ProSoft Technology MVI56-AFC User Manual
Page 235
MVI56-AFC ♦ ControlLogix Platform
MVI56-AFC Sample Logic
Liquid and Gas Flow Computer
User Manual
ProSoft Technology, Inc.
Page 235 of 316
February 25, 2011
Updating the High Precision Molar Analysis
To update the molar analysis with high precision data, follow these steps.
1 Set the stream number through
AFC56.Meters[ ].Analysis.High_Precision.Stream
2 Enter the molar analysis through
AFC56.Meters[0].Analysis.High_Precision.Components. For the example
below the components are set as C1 = 0.7 (70%) and N2 = 0.3 (30%)
3 Set the AFC56.Meters[0].Analysis.High_Precision.Enable value as 1
4 Observe AFC56.Meters[0].Analysis.High_Precision.Enable bit automatically
reset to 0
5 Refer to the AFC Manager to observe the updated molar analysis: