beautypg.com

ProSoft Technology MVI56-AFC User Manual

Page 239

background image

MVI56-AFC ♦ ControlLogix Platform

MVI56-AFC Sample Logic

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 239 of 316

February 25, 2011

12.3.12 Site Status

The ladder logic continuously reads the site status from the MVI56-AFC. The

following controller tags are used:

Information

Controller Tag

AFC56(16) Released

AFC56.Site_Status.AFC_ACTIVE

Checksum Alarms

AFC56.Site_Status.Checksum_Alarms

PLC Halted

AFC56.Site_StatusPLC_Halted

Cfg Changed

AFC56.Site_Status.Cfg_changed

Power Up

AFC56.Site_Status.Powerup

Cold Start

AFC56.Site_Status.ColdStart

12.3.13 Modbus Master

This block performs an arbitrary data transfer between the PLC and external

Modbus slaves connected to AFC port 3, provided that port 3 is configured as a

Modbus master. Any data transfer to or from a slave’s holding registers, input

registers, output coils, or input status may be implemented using this function;

equivalent Modbus function codes are 1, 2, 3, 4, 15, and 16. In addition,

capability is provided for access to a slave’s "long remote" (32-bit) registers

where the slave implements them; in particular, Daniel-style long integer (5000

series) and floating point (7000 series) registers are accessible. Any data words

not relevant to the command are ignored upon output (to the AFC) and zero upon

input (from the AFC).

This manual is related to the following products: