beautypg.com

3 orifice (differential) meter with gas product – ProSoft Technology MVI56-AFC User Manual

Page 288

background image

Reference

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 288 of 316

ProSoft Technology, Inc.

February 25, 2011

The cumulative status bits are defined as follows:

Offset

End Offset

00

Stream 1 active

01

Stream 2 active

02

Stream 3 active

03

Stream 4 active

11

Meter enabled

12

Backplane Communication Fault

13

Measurement Configuration Changed

14

Power up

15

Cold Start

The following 20 words (default configuration) will depend on the meter type and

product group as follows:

14.5.3 Orifice (Differential) Meter with Gas Product

Start Offset

End Offset

Data Format

Type

Description

10

11

Accumulator

Snapshot

Accumulator totalizer, net

12

13

Floating point

Snapshot

Accumulator residue, net

14

15

Floating point

Flow weighted average

Flow rate, net

16

17

Floating point

Flow weighted average

Temperature

18

19

Floating point

Flow weighted average

Pressure

20

21

Floating point

Flow weighted average

Differential pressure

22

Word

Flow weighted average

Relative density, e-4

23

Word

Flow weighted average

Compressibility, reference, e-4

24

Word

Flow weighted average

Compressibility, flowing, e-4

25

Word

Flow weighted average

Supercompressibility, e-4

26

Word

Flow weighted average

Velocity of approach factor, Ev, e-4

27

Word

Flow weighted average

Expansion factor, Y, e-4

28

Word

Flow weighted average

Coefficient of discharge, Cd, e-4

29

Word

(available)