ProSoft Technology MVI56-AFC User Manual
Page 273
MVI56-AFC ♦ ControlLogix Platform
Reference
Liquid and Gas Flow Computer
User Manual
ProSoft Technology, Inc.
Page 273 of 316
February 25, 2011
14.1.6 Hardware Specifications
Specification
Description
Backplane Current Load
800 mA @ 5 Vdc
3 mA @ 24 Vdc
Operating Temperature
0°C to 60°C (32°F to 140°F)
Storage Temperature
-40°C to 85°C (-40°F to 185°F)
Shock
30 g operational, 50 g non-operational
Vibration: 5 g from 10 Hz to 150 Hz
Relative Humidity
5% to 95% (with no condensation)
LED Indicators
Module Status, Backplane Transfer Status,
Application Status, Serial Activity
Debug/Configuration port (CFG)
CFG Port (CFG)
RJ45 (DB-9M with supplied cable), RS-232 only
Application ports (MODBUS 2 & MODBUS 3)
Full hardware handshaking control, providing radio, modem and multi-drop support
App Ports (MODBUS 2 &
MODBUS 3)
RJ45 (DB-9M with supplied cable)
RS-232, RS-485, RS-422 jumper selectable
RS-232 handshaking configurable
500 V Optical isolation from backplane
Shipped with Unit
RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable