ProSoft Technology MVI56-AFC User Manual
Page 181
MVI56-AFC ♦ ControlLogix Platform
MVI56-AFC Backplane Communication
Liquid and Gas Flow Computer
User Manual
ProSoft Technology, Inc.
Page 181 of 316
February 25, 2011
Pulse Frequency Integration with Liquid Product
Meter PV: Output Function Block
Meter PV: Input Function Block
Element
Attribute
Element
Attribute
0
Block ID: Function Code & Meter
Number
0
Block ID: Function Code, Meter
Number, Active Stream Number
1
Water % (see Note)
1
Meter Alarms (Bitmap)
2
Temperature LS (see Note)
2
Net Accumulator LS (double
integer)
3
Temperature MS
3
Net Accumulator MS (double
integer)
4
Pressure LS (see Note)
4
Net Flow Rate LS (float)
5
Pressure MS
5
Net Flow Rate MS (float)
6
Reserved
6
Gross Accumulator LS (double
integer)
7
Reserved
7
Gross Accumulator MS (double
integer)
8
Density LS (see Note)
8
Gross Standard Accumulator LS
(double integer)
9
Density MS
9
Gross Standard Accumulator MS
(double integer)
10
Meter Pulse Freq: Hz LS (float)
10
Mass Accumulator LS (double
integer)
11
Meter Pulse Freq: Hz MS (float)
11
Mass Accumulator MS (double
integer)
Note: During meter configuration you can select from up to 3 data format options (floating point,
scaled integer, 4 to 20 mA) for supplying in the OFB the process input values noted. See the
Special Notes section below for details.