9.5.2 Data Elements
Modbus Points
Point in
Modbus
Table
Mandatory or
Optional
Value
Description
slave
selection
Mandatory
P
Primary Slave
V
Virtual Slave
register
bank
Mandatory
h
holding registers
i
input registers
register
address
Mandatory
nnnnn
or,
+nnn
A register address has
the form "nnnnn" which
is the 5-digit offset (0-
based) of the register in
the selected bank; a
register address may
also have the form
"+nnn" where "nnn" is
the 3-digit offset (0-
based) of the register in
a block of registers
which block is located
more globally by
accompanying text.
byte
selection
Optional
L
low-order byte
H
high-order byte
bit number Optional
/nn
Bit number, if present, is
"/nn" where "nn" is the
number of the bit in the
16-bit register or 8-bit
byte, with bits numbered
from 0 at the low-order
end of the register or
byte.
"Ph00146" identifies the 16-bit register at offset 146 in the Primary Slave’s
holding register bank.
"Ph00006H/01" identifies bit 1 of the high-order byte of Primary Slave holding
register 6; this byte is already allocated in the AFC as the Site Extended
Status byte. This bit can be alternately addressed as "Ph00006/09", but the
AFC internally treats the two bytes as distinct.
"Ph00200/05" identifies bit 5 of Primary Slave holding register 200; this bit is
an as-yet unallocated bit in the Site Signals register.
"LDW+000" identifies the first of a block of registers in the Primary Slave
holding register bank and optionally in the Virtual Slave holding register bank,
which block’s absolute location is determined according to accompanying
text.