6.3.1 Example
The following table shows how the data types are implemented if a write function
is selected and the item count is configured with a value of 10 (decimal):
Data Type
Register
Type
Modbus
Function
Number of
Coils
Number of
Bytes
Number of
Registers
Number of words
(16-bits)
transferred
Bit
Coil
15
10
2
-
1
Word
Holding
16
-
20
10
10
Long
Holding
16
-
40
20
20
Long Remote
Holding
16
-
40
10
20
Note: The number of coils, bytes, and registers are part of the Modbus request (functions 15 and
16) according to the Modbus specification.
The following table shows how the data types are implemented if a read function
is selected and the item count is configured with a value of 10 (decimal):
Data Type
Register Type
Modbus Function
Number of Registers
Bit
Coil
1
10
Bit
Input
2
10
Word
Holding
3
10
Word
Input
4
10
Long
Holding
3
20
Long
Input
4
20
Long Remote
Holding
3
10
Long Remote
Input
4
10
Note: The number of registers is part of the Modbus request according to the Modbus
specification.
Refer to the ladder logic section for your module for more information about the
Modbus Master block.