Description
This block supplies the analysis for AGA8 and GPA8173 calculations, in low-
precision form as integers scaled to 4 decimal places. Upon change of analysis
the meter undergoes a "characterization" calculation, which is performed before
this block is returned; if the analysis has not changed, no characterization is
required, and this block is returned immediately.
Element
Attribute
Element
Attribute
0
Block ID - Function Code & Meter Number
0
Block ID - Function Code, Meter Number,
Active Stream Number
1
Propane - C1
Reserved
2
Nitrogen - N2
Reserved
3
Carbon dioxide -CO2
Reserved
4
Methane - C2
Reserved
5
Propane - C3
Reserved
6
Water - H2O
Reserved
7
Hydrogen Sulfide - H2S
Reserved
8
Hydrogen - H2
Reserved
9
Carbon Monoxide - CO
Reserved
10
Oxygen - O2
Reserved
11
Iso Butane - IC4
Reserved
12
Butane - C4
Reserved
13
Iso Pentane - IC5
Reserved
14
Pentane - C5
Reserved
15
Hexane - C6
Reserved
16
Heptane - C7
Reserved
17
Octane - C8
Reserved
18
Nonane - C9
Reserved
19
Decane - C10
Reserved
20
Helium - He
Reserved
21
Argon - Ar
Reserved
22
Neo Pentane - C5
Reserved
23
Ux User 1
Reserved
24
Ux User 2
Reserved
The input block always returns an alarm indicator as part of the block id; the
remaining 24 words are freely selectable from the entire meter database, with the
default selection being nothing (all zero).
An application should not implement both 16-bit and 32-bit analysis blocks for the
same stream. The AFC will convert the analysis, whether 16-bit or 32-bit, to the
precision configured for the analysis slot assigned to the targeted stream, though
best practice would be to use the analysis block that matches the configured
precision.