ProSoft Technology MVI56-AFC User Manual
Page 108
Archives
MVI56-AFC ♦ ControlLogix Platform
User Manual
Liquid and Gas Flow Computer
Page 108 of 316
ProSoft Technology, Inc.
February 25, 2011
Control
Description
Select Meter
Select the meter number
Select Archives
Select the archive type
Ages
Select the first archive to be added or removed
To
Select the last archive to be added or removed
Add
Add the selected archives to the grid, fetching as necessary
Remove
Remove the selected archives from the grid
Connect
Connect to the module, if necessary
Upd Current
Update the current archive
Update All
Update all archives in the grid
Clear
Clear the grid
Log
Create a log file containing the archived data
Print the archives to the local printer
Plot
Display a plot of two datum points from archives in the grid
The following shows an example of an archive report generated by the AFC
Manager:
AFC-56(16) Daily Archive Date: 16-09-2002 16:26:41
Site Name: MVI Flow Station
Project: AFC
___________________________________________________________________________
Meter 1:
Tag M01
Archive 0
Closing timestamp of archive 2002-04-27.23:59:08
Opening timestamp of archive 2002-04-27.00:00:02
Status bitmap (details below) 00h
Alarms bitmap (details below) 0000h
Flowing period 86346
Event counter 53
Net accumulator (x f3) 604
Net accumulator residue (x f3) 0,6703186
Net flow rate (x f3/h) 40247,93
Temperature (°F) 14,99997
Pressure (psig) 999,9995
Differential pressure (hw) 21,99997
Relative density (60°F/60°F) 0,7404
Reference compressibility 0,9989
Flowing compressibility 0,9051
Fpv 1,0505
Velocity of approach factor Ev 1,0328
Expansion factor Y 0,9997
Discharge coefficient 0,6043
Alarm Bits
bit 0 Temperature input out of range -
bit 1 Pressure input out of range -