beautypg.com

Table 3-2. fault recovery configuration, Fault recovery configuration -20, Warning – KEPCO KLP Series User Manual, Rev 4 User Manual

Page 62

background image

3-20

KLP091313

ming ports. Recovery cannot be initiated by toggling the remote inhibit line at the analog
programming port. This option provides greater operator convenience by eliminating the
need to reboot the power supply while preserving a safe response (output off), but it is
the user’s responsibility to NOT attempt multiple consecutive restarts without eliminating
the fault condition.

• AUTOmatic - When a fault configured for AUTO recovery is detected, the output is dis-

abled as long as the fault condition exists. Once the fault condition is no longer present
(e.g., the unit has cooled down after an overtemperature fault) the output is enabled at
the last actual settings for voltage and current, as opposed to setpoints (see PAR.
3.2.10.3 for Last Setting Recall). To alert the user to this risk, if any fault is set to AUTO
recovery, the status display briefly shows AUTO after a) any fault recovery, b) any output
enable action or c) upon leaving Setpoint mode. In addition, if AUTO recovery is selected
for source power failure (PWR) faults, the status display flashes AUTO for one second as
part of the power-up sequence.

WARNING

When AUTOmatic recovery is selected, upon removal of the fault condi-

tion the output recovers to the conditions (programmed voltage/current

levels and output enabled/disabled) that existed when the fault was

detected. For this reason, AUTOmatic recovery mode is best suited to

applications where it is anticipated that the output is always enabled.

For safety reasons, when servicing circuits powered by the output

always switch the KLP front panel circuit breaker OFF or activate

Remote Inhibit (see PAR. 3.2.6).

If more than one fault occurs, the fault with the lowest risk level determines the unit’s response,
however multiple faults will cause the output to be off upon recovery, even if set to AUTO.

The factory default configuration is PROTECT for all faults. Note that some faults have limited
options. The recovery options for each fault are presented in Table 3-2:

NOTE: When using a master/slave configuration, all faults are set to PROTECT and power to

both units must be cycled to clear a fault.

TABLE 3-2. FAULT RECOVERY CONFIGURATION

Fault

Auto Recovery Options

PROTECT

SAFE

AUTO

OVP (Overvoltage Protection fault)

YES

YES

---

OCP (Overcurrent Protection fault)

YES

YES

---

OLF (Output Lead Fault)

YES

YES

---

TEMP (Temperature fault)

YES

YES

YES

PWR (Loss of source power fault)

YES

YES

YES

FAN (Fan failure fault)

YES (not configurable)

---

---

This manual is related to the following products: