Table 1-3. klp specifications, Klp specifications -4 – KEPCO KLP Series User Manual, Rev 4 User Manual
Page 16
1-4
KLP 091313
TABLE 1-3. KLP SPECIFICATIONS
SPECIFICATION
RATING/DESCRIPTION
CONDITION/COMMENT
INPUT CHARACTERISTICS
a-c voltage(1)
nominal
100-240 Va-c
Single Phase.
range
90-265 Va-c
Wide Range; contact factory for opera-
tion to 265V a-c.
Frequency
nominal range
50-60 Hz
maximum
45-440 Hz
Increased Leakage above 66 Hz.
Power Factor
typical
0.99
Meets EN 61000-3-2.
Maximum Input Current
120 Va-c
13A rms
Rated load (1200W).
240 Va-c
6.5A rms
Rated load (1200W).
Inrush Current
265 Va-c
40A
Peak
132 Va-c
20A
Peak
Input Fusing
Circuit Breaker
2-line
Low a-c Protection
87V a-c, Self protected
Output hold up
typical
10 milliseconds
Ride through.
Leakage Current
115 Va-c, 60Hz
1.2mA max
230 Va-c 50Hz
2.3mA max
Electromagnetic
compatibility
Emissions
CISPR11, Class A
Class B Conducted
Immunity
EN 61326-1, Table 2
Industrial Environment
OUTPUT CHARACTERISTICS
Type of stabilizer
CV/CC
Voltage/Current
Adjustment range
voltage
0-100% of rated voltage
No minimum load required.
current
minimum to 100% of rated current
No minimum load required. See Table
1-2 for minimum programmable current.
Source effect
voltage
0.01% Emax
Over full source range.
current
0.01% Imax
Load effect
voltage
0.02% Emax
Over full load range.
current
0.05% Imax
Temperature effect
voltage
0.01%/deg C
0-50 deg C
current
0.01%/deg C
Time effect (drift)
voltage
0.02%/24hr
After 30 min warmup.
current
0.02%/24hr
Error sensing
0.25 volts per wire
Above rated output. Contact factory for
larger margins.
Isolation voltage
600 Vd-c or peak
(100V for 10V, 20V and 36V models)
Either output terminal to ground.
(1) Contact factory for details on operation from d-c input.