PHYSICAL CHARACTERISTICS
Dimensions
English 1.735”H x 19"W x 17.5"D
Depth excluding connectors and termi-
nal blocks (see Figure 1-3).
metric 44.45 x 482.6 x 443.7 mm
Weight
English 15 lbs
metric 6.82kg
Dielectric strength
Input - Chassis
2121V d-c
Output - Chassis
2121V d-c
(1250V d-c 10V, 20V, and 36V models)
Input - Output
4242V d-c
(2500V d-c 10V, 20V, and 36V models)
Source power connector
IEC 320-C19 appliance inlet
250 Va-c, 16A (VDE);
125V a-c, 20A (UL)
Load connections
10-36V models Nickel plated copper busbar with inte-
gral threaded stud (1/4-20-1/2in.)
Provision for safety covers.
75-600V models Shock-safe Euroblock, single conduc-
tor size: 20-10AWG (0,5 - 5,0 mm2)
Analog programming port.
15 pin D-sub
Digital programming ports
primary Standard GPIB connector
IEEE 488.2 (GPIB)
secondary 9 pin D-sub
RS 232 (standard Models only)
secondary RJ 45
LAN (E-Series Models Only)
Feedback/Control Input
5 position low profile Euroblocks
PROGRAMMING CHARACTERISTICS - LOCAL
Local control
rotary encoders
Panel mounted.
Local control resolution
Coarse ~100 LSB/step
Depress control for Fine resolution
Fine 1 LSB/step
Setting range
0-100% of rating
KLP will automatically adjust limit to
maintain 1200 W maximum,
Power up settings
voltage defaults to zero
See PAR. 3.2.10.3 for Last Settings
Recall function.
current defaults to min. value (See Table 1-2)
Protection Limits
Overvoltage 20-120% of Emax
Programmable; accessed via front
panel protect switch or SCPI command
over digital bus.
Overcurrent 72-120% of Imax