4 overvoltage/overcurrent protection, 6 storage of user-programmed active settings, 7 user-programmed sequences – KEPCO KLP Series User Manual, Rev 4 User Manual
Page 23: 8 last setting recall, 9 built-in protection, Overvoltage/overcurrent protection -11, Storage of user-programmed active settings -11, User-programmed sequences -11, Last setting recall -11, Built-in protection -11
KLP 091313
1-11
1.5.4
OVERVOLTAGE/OVERCURRENT PROTECTION
Overvoltage and Overcurrent protection values can be individually programmed. If the output
voltage/current exceeds the overvoltage/overcurrent protection value, the protection circuit
latches the output off, flashes an overvoltage (OVP) or overcurrent (OCP) error message on the
status display and sets a status bit that can be retrieved through the RS 232 [standard models
only], LAN [E-Series models only], or GPIB port. The N.O. and N.C. contacts of the relay pro-
vide status flags via the Analog I/O port connector. Refer to PAR. 3.2.17.1 for more information.
1.5.5
USER-DEFINED VOLTAGE/CURRENT LIMITS (VIRTUAL MODELS)
The KLP Power Supply can be programmed to User-defined values that can be lower than the
maximum values. For example, the KLP 36-60 will automatically be limited to 1200 Watts as
illustrated in Figure 1-2, however arbitrary limits, e.g., 40A@30V or 30A@35V can be estab-
lished. Once the limits are set, setting values exceeding the limit values will not be accepted.
Refer to PAR. 3.2.9 for more information.
1.5.6
STORAGE OF USER-PROGRAMMED ACTIVE SETTINGS
The KLP Power Supply contains 40 memory locations that can be used to store active settings.
This feature is only available via digital remote programming. Values are stored in the nonvola-
tile memory, and are retained when the unit is turned off (refer to PAR 3.3.2 for more informa-
tion).
1.5.7
USER-PROGRAMMED SEQUENCES
The KLP Power Supply contains 100 memory locations for programming sequences that can
program the KLP to produce a variety of sequential output operations. Each memory location
accommodates a value for voltage and current and a dwell time (how long the parameter is to
be in effect). Values are stored in the volatile memory, and are lost when the unit is turned off
(refer to PAR 3.3.2 for more information).
1.5.8
LAST SETTING RECALL
The KLP Power supply has the ability to retain the last voltage and current setpoints pro-
grammed before the unit is shut off. A DIP switch selection (position 3) allows the user to deter-
mine whether the power supply is set to 0V, minimum current or the retained voltage and current
setpoints upon the next power-up sequence. Refer to Table 2-2 and PAR. 3.2.10.3 for more
information.
1.5.9
BUILT-IN PROTECTION
KLP Series Power Supplies provide built-in protection against the system faults listed below. In
each case, a detected fault results in immediate latched shutdown of the power supply output. In
addition, the status display flashes the appropriate indication and the status bit is set for retrieval
through either of the digital programming ports. If the internal relay is configured for FAULT
mode (factory default setting, see PAR. 3.2.17.1) the relay will toggle to provide a composite
fault indication at the analog programming port. The indication time is limited by internal hold-up
capacity for PWR faults (as the unit shuts down, when power is no longer sufficient to power the
relay it de-energizes.
a. Overtemperature (OTP). Monitors heatsink temperature; trips if it exceeds factory set limit.
b. Overvoltage (OVP) or overcurrent (OCP) at the output. (See PAR. 3.2.11)