5.1 iQpump Basic Programming Parameters

90

YASKAWA TM.iQp.01 iQpump Drive User Manual

Figure 5.2

Figure 5.2 Digital Operator Auto Setpoint

If you want the iQpump drive to follow an “Auto Setpoint” set by the analog input: Set b1-01 = “1: Terminals,” and connect a
potentiometer or external signal to the iQpump drive. Refer to

Figure 5.3

for connection diagram for the setpoint potentiometer.

Figure 5.3 Setpoint Potentiometer Connection Diagram

Refer to

Figure 5.4

for the connection diagram for an external analog signal setpoint reference.

Note: When b1-01 = 1 (terminals) and P5-01 = 0 (hand mode reference source), the setpoint and the hand reference are

determined by the external analog signal.