5.2 Pump Basic

YASKAWA TM.iQp.01 iQpump Drive User Manual

127

5.2

Pump Basic

Parameter Overview — P1 Group

Table 5.6

P1 Pump Minimum Speed and No-Flow Detection

The iQpump controller can be programmed to operate the pump motor at a user set minimum speed and has three independent built-in
functions to protect the pump against a no-flow condition.

The following sections describe each of these functions.

Set Minimum Pump Speed (P1-06)

The required minimum operating speed of the pump motor can be set with Parameter P1-06 Minimum Pump Frequency.

Table 5.7

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

P1-01

0600H

Pump Mode
Pump Mode

Select type of control operation.
0: Drive Only (Simplex)
1: Drive + 1 Pump (Duplex)
2: Drive + 2 Pumps (Triplex)

0 to 2

0

Programming

P1-02

<0032>

0601H

System Units
System Units

0: WC:InchOfWater
1: PSI:lb/SqrInch
2: GPM:Gallons/Min
3: F:DegFarenheit
4: CFM:Cubic ft/Min
5: CMH:Cubic m/Hr
6: LPH:Liters/Hr
7: LPS:Liters/sec.
8: Bar:Bar
9: Pa:Pascals
10: C:DegCelsius
11: Ft: Feet

<0032>

12: %: Percent

0 to 12

1

Pump Quick

Setup

P1-03

0602H

Feedback Device
Scaling
Fb Dev Scaling

Scaling of feedback device in user units (P1-02 = 1, e.g. 150PSI).
Digits 1 through 4 set the maximum feedback number. Digit 5
determines the number of decimal places.
Digit 5 = 0: Number format is XXXX
Digit 5 = 1: Number format is XXX.X
Digit 5 = 2: Number format is XX.XX
Digit 5 = 3: Number format is X.XXX
Examples:
01000 = 1000
10300 = 300.0
25000 = 50.00
32000 = 2.000

1 to 36000

(system

units P1-

02)

00145

Pump Quick

Setup

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

P1-06



0605H

Minimum Pump
Frequency
Min. Pump Freq.

Minimum drive frequency when operated in the auto mode.
Programmed value will limit minimum PID output. Minimum value
has to be programmed to a value smaller than P3-09 and P3-10 when
Drive is operating in the multiplex mode (P1-01).

0 to 120Hz 35.0Hz

Pump Quick

Setup