6.1 Fault Detection

138

YASKAWA TM.iQp.01 iQpump Drive User Manual

LF

Output Phase Loss

Output Open-phase

An open-phase occurred at the iQpump output.
This fault is detected when output current has
exceeded 5% imbalance.

There is a broken wire in the output
cable.

There is a broken wire in the motor

winding.

The output terminals were loose.

Check the wiring to the motor.

Check the motor for phase-to-ground
short.

The motor being used has a
capacity less than 5% of the
iQpump’s maximum motor

capacity.

Check the motor and iQpump capacity.

Low impedance motor was used.

Add additional impedance.

Parameter E2-03 set incorrectly.

Adjust E2-03 to a lower value.

LL3

Loss of Load Det 1

Loss of Load Detection 1

iQpump output current < L6-02 for more than the
time set in L6-03.

Motor is underloaded.

Ensure the values in L6-02 and L6-03
are appropriate.
Check application/machine status to

eliminate fault.

OC

Over Current

Overcurrent

iQpump output current exceeded the overcurrent

detection level (approximately 180% of iQpump
rated output current).

Shorted iQpump output phase-to-
phase, shorted motor, locked rotor,

load too heavy, accel/decel time
too short, contactor on the iQpump
output is opened and closed, a

special motor or a motor with a
FLA rating larger than iQpump
rated output current.

Remove the motor and run the iQpump
without the motor.
Check the motor for a phase-to-phase
short.
Check the iQpump for a phase-to-phase

short at the output.
Verify C1-01 to C1-06 are set correctly.
Check load conditions.

OH1

Heatsink MAX

Temp

Cooling Fin/Cooling Fin Fan Overheat

The temperature of the iQpump cooling fin
exceeded the temperature programmed in
parameter L8-02, and L8-03 = 0-2.

Cooling fan(s) are not working,
high ambient temperature, a heat

source is too close to the iQpump.

Check for dirt build-up on the fans and
cooling fins.
Reduce the ambient temperature around
the iQpump.

iQpump Internal Cooling Fan.

Remove the heating unit/Replace the
cooling fan.

OH3

Motor Overheat 1

Motor Overheating Alarm

The iQpump stops or continues operation

according to the setting of L1-03.

Overheating of motor as measured

by motor thermistor.

Recheck the cycle time and the size of

the load.
Recheck the accel/decel time (C1-01 to
C1-06).
Recheck the V/F pattern (E1-01 thru
E1-13).
Recheck the motor rated current value

(E2-01).

OH4

Motor Overheat 2

Motor Overheating Fault

The iQpump stops operation according to the
setting of L1-04.

Overheating of motor as measured
by motor thermistor.

Recheck the cycle time and the size of
the load.
Recheck the accel/decel time (C1-01 to
C1-06).
Recheck the V/F pattern (E1-01 thru

E1-13).
Recheck the motor rated current value
(E2-01).

OL1

Motor Overloaded

Motor Overload

Designed to protect the motor. Fully adjustable
from parameter E2-01.

The load is too large. The cycle
time is too short at the accel/decel
time.

Recheck the cycle time and the size of
the load as well as the times set in C1-01
and C1-03 to C1-06.

The voltage of the V/F pattern is

high.

Review the V/F pattern parameters,

E1-01 thru E1-13.

Motor rated current setting is
improper.

Check the motor rated current value in
E2-01.

Digital

Operator Display

Description

Cause

Corrective Action