170

YASKAWA

TM.iQp.01 iQpump Drive User Manual

Preset Reference

d1-01



0280H

Setpoint Reference 1
Setpoint 1

Digital preset setpoint reference 1. Used when b1-01 = 0 and when in
“hand” mode. Setting units are affected by P1-02.

1 to P1-03

Value

0

Programming

36

d1-02



0281H

Setpoint Reference 2
Setpoint 2

Digital preset setpoint reference 2. Selected via multi-function input
terminals. Setting units are affected by P1-02.

0

Programming

36

d1-03



0282H

Setpoint Reference 3
Setpoint 3

Digital preset setpoint reference 3. Selected via multi-function input
terminals. Setting units are affected by P1-02.

0

Programming

36

d1-04



0283H

Setpoint Reference 4
Setpoint 4

Digital preset setpoint reference 4. Selected via multi-function input
terminals. Setting units are affected by P1-02.

0

Programming

36

d1-17



0292H

Jog Frequency Reference
Jog Reference

Jog reference used when a jog is selected via the LCD operator keypad.
This parameter is not available with the HOA operator. Setting units
are affected by o1-03.

0

Programming

37

 Denotes that parameter can be changed when the drive is running.

Reference Limits

d2-01

0289H

Frequency Reference
Upper Limit
Ref Upper Limit

Determines maximum speed command, set as a percentage of
parameter E1-04. If speed command is above this value, actual Drive
speed will be limited to this value. This parameter applies to all speed
command sources.

0.0 to
110.0

100.0% Programming

38

d2-02

028AH

Frequency Reference
Lower Limit
Ref Lower Limit

Determines minimum speed command, set as a percentage of
parameter E1-04. If speed command is below this value, actual Drive
speed will be set to this value. This parameter applies to all speed
command sources.

0.0 to
110.0

0.0%

Programming

38

d2-03

0293H

Master Speed Reference
Lower Limit
Ref1 Lower Limit

Determines the minimum speed command, set as a percentage of
parameter E1-04. If speed command is below this value, actual Drive
speed will be set to this value. This parameter only applies
to analog inputs A1 and A2.

0.0 to
110.0

0.0%

Programming

38

Jump Frequencies

d3-01

0294H

Jump Frequency 1
Jump Freq 1

These parameters allow programming of up to three prohibited
frequency points for eliminating problems with resonant vibration of
the motor / machine. This feature does not actually eliminate the
selected frequency values, but will accelerate and decelerate the motor
through the prohibited bandwidth.

0.0 to
200.0

0.0 Hz

Programming

39

d3-02

0295H

Jump Frequency 2
Jump Freq 2

0.0 Hz

Programming

39

d3-03

0296H

Jump Frequency 3
Jump Freq 3

0.0 Hz

Programming

39

d3-04

0297H

Jump Frequency Width
Jump Bandwidth

This parameter determines the width of the deadband around each
selected prohibited frequency point. A setting of “1.0” will result in a
deadband of +/- 1.0 Hz.

0.0 to 20.0

1.0 Hz

Programming

39

V/F Pattern

E1-01

0300H

Input Voltage Setting
Input Voltage

Set to the nominal voltage of the incoming line.

155 to

255.0

(240V)

310 to

510.0

(480V)

240 V

480 V

Programming

40

E1-03

0302H

V/F Pattern Selection
V/F Selection

0: 50 Hz
1: 60 Hz Saturation
2: 50 Hz Saturation
3: 72 Hz
4: 50 Hz VT1
5: 50 Hz VT2
6: 60 Hz VT1
7: 60 Hz VT2
8: 50 Hz HST1
9: 50 Hz HST2
A: 60 Hz HST1
B: 60 Hz HST2
C: 90 Hz
D: 120 Hz
F: Custom V/F
FF: Custom w/o limit

0 to FF

F

Programming

40

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.