beautypg.com

O1 monitor configuration, O1-01 user monitor selection, O1-02 power-on monitor – Yaskawa iQpump Drive User Manual User Manual

Page 122

background image

5.1 iQpump Basic Programming Parameters

122

YASKAWA TM.iQp.01 iQpump Drive User Manual

o1 Monitor Configuration

o1-01 User Monitor Selection

Setting Range:

6 to 94

Factory Default: 6

o1-02 Power-On Monitor

When the iQpump drive is powered up, three monitors are displayed on the digital operator. The first and largest monitor is the “Power-
On” monitor. The factory default “Power-On monitor” is Speed Command (U1-01). Below the Speed Command monitor are the next two

sequential monitors, Output Frequency (U1-02) and Output Current (U1-03). Pressing the INCREASE key once scrolls the monitors to

show the User Monitor as selected by o1-01. The factory default for o1-01 is the Output Voltage monitor (U1-06).

The active monitor displayed when the iQpump drive is powered on can be changed to either be U1-01 (Speed Command), U1-02

(Output Frequency), U1-03 (Output Current), or the User Monitor. Whichever monitor is selected as the Power-On top monitor, the two

monitors displayed below it are the next two sequential monitors. See example below.

Setting

Description

6

Output Voltage (factory default)

7

DC Bus Voltage

8

Output Power

10

Input Terminal Status

11

Output Terminal Status

12

Drive Operation Status

13

Cumulative Operation Time

14

Software Number

15

Terminal A1 Input Voltage

16

Terminal A2 Input Voltage

18

Motor Secondary Current (Iq)

20

Output Frequency After Soft Start

24

PI Feedback Value

28

CPU Number

34

First Parameter Causing an OPE

36

PI Input

37

PI Output

38

PI Setpoint

39

Memobus Communication Error Code

40

Heatsink Cooling Fan Operation Time

90

Pump Setpoint

91

Pump Feedback

92

Pump Status

93

Total Setpoint Compensation

94

Motor Speed

Setting

Description

1

Frequency Reference (factory default)

2

Output Frequency

3

Output Current

4

User Monitor (set by o1-01)

-DRIVE- Rdy

Frequency Ref

U1-

01

= 60.00Hz

- - - - - - - - - - - - - - - - - - - - - - - - - - - - -

U1-02= 60.00Hz

U1-03= 10.05A

Active Monitor

Next two
sequential
monitors

Active Monitor Title

Output Frequency

Output Current