Yaskawa iQpump Drive User Manual User Manual
Page 216

D.3 Modbus Data Tables
216
YASKAWA
TM.iQp.01 iQpump Drive User Manual
002CH
Drive status
Bit 0
Operation 1: Operating
Bit 1
Zero speed 1: Zero speed
Bit 2
Frequency agree 1: Matched
Bit 3
Desired frequency agree 1: Matched
Bit 4
Frequency detection 1 1: Output frequency ≤ L4-01
Bit 5
Frequency detection 2 1: Output frequency ≥ L4-01
Bit 6
Drive startup completed 1: Startup completed
Bit 7
Low voltage detection 1: Detected
Bit 8
Baseblock 1: Drive output baseblock
Bit 9
Frequency reference mode 1: Not communication 0: Communication
Bit A
Run command mode 1: Not communication 0: Communication
Bit B
Overtorque detection 1: Detected
Bit C
Frequency reference lost 1: Lost
Bit D
Retrying error 1: Retrying
Bit E
Error (including Modbus communications time-out) 1:Error occurred
Bit F
Modbus communications time-out 1: Timed out
002DH
Multi-function digital output status
Bit 0
Multi-function digital output 1 (terminal M1-M2) 1: ON 0: OFF
Bit 1
Multi-function digital output 2 (terminal M3-M4): 1: ON 0: OFF
Bit 2
Not used
Bits 3 to F
Not used
002EH - 0030H
Not used
0031H
Main circuit DC voltage
0032H - 0037H
Not used
0038H
PI feedback level (Input equivalent to 100%/Max. output frequency; 10/1%; without sign)
0039H
PI input level (±100%/±Max. output frequency; 10/1%; with sign)
003AH
PI output level (±100%/±Max. output frequency; 10/1%; with sign)
003BH
CPU software number
003CH
Flash software number
003DH
Communication error details
Bit 0
CRC error
Bit 1
Invalid data length
Bit 2
Not used
Bit 3
Parity error
Bit 4
Overrun error
Bit 5
Framing error
Bit 6
Time-out
Bits 7 to F
Not used
003EH
KVA setting
003FH
Control method
Note: Communication error details are stored until an error reset is input (errors can be reset while the Drive is operating).
Register No.
Contents