B.3 Capacity Related Parameter Values
B.3 Capacity Related Parameter Values
The following tables detail the factory default settings for the parameters that are affected by the setting of parameter o2-04.
Table B.3 208/240 VAC iQpump Drives
Drive Model
CIMR-P7U-107 Nominal Hp
Factory
Default
for
b8-04
Factory
Default
for
C6-02
<0032>
Factory
Default
for
E2-01
Factory
Default
for
E2-03
Factory
Default
for
E2-05
Factory
Default
for
L2-02
Factory
Default
for
L2-03
Factory
Default
for
L2-04
Factory
Default
for
L8-02
Factory
Default
for
L8-06
20P4
0.5/0.75
288.2
8 kHz
1.9
1.2
9.842
0.1
0.1
0.3
95
° C
5
20P7
2
223.7
8 kHz
3.3
1.8
5.156
0.1
0.2
0.3
95
° C
7.5
21P5
1.5/2
169.4
8 kHz
6.2
2.8
1.997
0.2
0.3
0.3
95
° C
10
22P2
3
156.8
8 kHz
8.5
3.0
1.601
0.3
0.4
0.3
100
° C
12
23P7
5
122.9
8 kHz
14.0
4.5
0.771
0.5
0.5
0.3
95
° C
12
25P5
7.5
94.75
8 kHz
19.6
5.1
0.399
1.0
0.6
0.3
95
° C
10
27P5
10
72.69
8 kHz
26.6
8.0
0.288
1.0
0.7
0.3
95
° C
17
2011
15
70.44
8 kHz
39.7
11.2
0.230
1.0
0.8
0.3
95
° C
21
2015
20
63.13
8 kHz
53.0
15.2
0.138
2.0
0.9
0.3
90
° C
17
2018
25
57.87
8 kHz
65.8
15.7
0.101
2.0
1.0
0.6
100
° C
15
2022
30
51.79
8 kHz
77.2
18.5
0.079
2.0
1.0
0.6
90
° C
24
2030
40
46.27
8 kHz
105.0
21.9
0.064
2.0
1.1
0.6
90
° C
20
2037
50
38.16
5 kHz
131.0
38.2
0.039
2.0
1.1
0.6
95
° C
18
2045
60
35.78
5 kHz
160.0
44.0
0.030
2.0
1.2
0.6
100
° C
20
2055
75
31.35
8 kHz
190.0
45.6
0.022
2.0
1.2
0.1
105
° C
17
2075
75/100
23.10
2 kHz
260.0
72.0
0.023
2.0
1.3
0.1
110
° C
16
2090
125
20.65
2 kHz
260.0
72.0
0.023
2.0
1.5
0.1
100
° C
18
2110
150
18.12
2 kHz
260.0
72.0
0.023
2.0
1.7
0.1
95
° C
20
Note:
b8-04 = Energy Savings Coefficiant
C6-02 = Carrier Frequency
E2-01 = Motor Rated Current
E2-03 = Motor No-Load Current
E2-05 = Motor Line-to-Line Resistance
L2-02 = Momentary Power Loss Ride-Thru Time
L2-03 = Momentary Power Loss Minimum Base Block Time
L2-04 = Momentary Power Loss Voltage Recovery Ramp Time
L8-02 = Overheat Pre-Alarm Level
L8-06 = Input Phase Loss Detection Level