4.7 High Feedback Level Alarm and Fault Setup

82

YASKAWA TM.iQp.01 iQpump Drive User Manual

Figure 4.7

Example: Constant Pressure System

System Units set to PSI (P1-02 = PSI)
System Setpoint set for 80 PSI

Pressure Transducer: 150 PSI

Desired Operation:
Pump System should show High Feedback Alarm when feedback level rises above 90 PSI and fault the system if the feedback level stays

there for more than 30 sec.

Solution: Program P1-09 to 90 PSI and P1-10 to 30 sec.

Note: High feedback detection is active during running in both Hand and Auto Mode.

FAULT
LFB

ALARM
LFB

NORMAL

TIME

P1-10

P1-10

FEEDBACK

High

Level
P1-09

P1-13

Hysteresis

ALARM
LFB