TM.iQp.01 iQpump Drive User Manual
181
L8-12
04B8H
Ambient Temperature 
Setting
Ambient Temp
When the Drive is installed in an ambient temperature exceeding its 
rating, Drive overload (OL2) protection level is reduced.
45 to 60°C
45°C
Programming
111
L8-15
04BBH
OL2 Characteristic 
Selection at Low Speeds
OL2 Sel @ L-Spd
This parameter assists in protecting the output transistor junctions from 
overheating when output current is high and output frequency is low.
0: Disabled
1: Enabled (L8-18 is active)
0 or 1
1
Programming
111
L8-18
04BEH
Soft CLA Selection
Soft CLA Sel
Enables and disables current limit “A”.
0: Disabled
1: Enabled.
0 or 1
1
Programming
112
L8-19 04BFH
OH Frequency Reference 
Reduction Level
Fref During OH
Sets the amount of frequency reference reduction when an Overheat 
Pre-alarm (OH) is detected.
0.0 to 
100.0
20.0%
Programming
112
Hunting Prev
n1-01
0580H
Hunting Prevention 
Selection
Hunt Prev Select
0: Disabled (Hunting prevention function disabled.)
1: Enabled (Hunting prevention function enabled.)
If the motor vibrates while lightly loaded, hunting
prevention may reduce the vibration. There is a loss of responsiveness 
if hunting prevention is enabled.
0 or 1
1
Programming
113
n1-02
0581H
Hunting Prevention Gain 
Setting
Hunt Prev Gain
Gain setting for the Hunting Prevention Function.
If the motor vibrates while lightly loaded and n1-01=1, increase the 
gain by 0.1 until vibration ceases. If the motor stalls while n1-01=1 
decrease the gain by 0.1 until the stalling ceases.
0.00 to
2.50
1.00
Programming
113
High Slip
n3-01
0588H
High-Slip Braking 
Deceleration Frequency 
Width
HSB Decel Width
Sets how aggressively the Drive decreases the output frequency as it 
stops the motor. If overvoltage (OV) faults occur during HSB, this 
parameter may need to be increased.
Note:
Function Deactivated
1.0 to 20.0
5%
Programming
113
n3-02
0589H
High-Slip Braking 
Current Limit
HSB Current Ref
Sets the maximum current to be drawn during a HSB stop. Higher n3-
02 settings will shorten motor stopping times but cause increased 
motor current, and therefore increased motor heating.
.Note: Function Deactivated
100.0 to
200.0
150%
Programming
113
n3-03
058AH
High-Slip Braking Dwell 
Time at Stop
HSB DwelTim@ Stp
Sets the amount of time the Drive will dwell at E1-09 (Minimum 
Frequency). If this time is set too low, the machine inertia can cause the 
motor to rotate slightly after the HSB stop is complete and Drive 
output is shut off.
.Note: Function Deactivated
0.00 to
10.0
1.0 sec
Programming
113
n3-04
058BH
High-Slip Braking 
Overload Time
HSB OL Time
Sets the time required for a HSB Overload Fault to occur when the 
Drive output frequency does not change for some reason during a HSB 
stop. Normally this does not need to be adjusted.
Note:
Function Deactivated
30.0 to 
1200.0
40 sec
Programming
113
Monitor Select
o1-01
0500H
User Monitor Selection
User Monitor Sel
Selects which monitor will be displayed upon power-up when o1-02 = 
4.
6 to 94
6
Programming
114
o1-02
0501H
User Monitor Selection 
After Power-Up
Power-On Monitor
Selects which monitor will be displayed upon power-up.
1: Auto: Setpoint
2: Output Freq
3: Output Current
4: User Monitor (set by o1-01)
1 to 4
1**
Programming
114
o1-05
0504H
LCD Brightness 
Adjustment
LCD Contrast
0 to 5
3
Programming
115
o1-06
0517H
User Monitor Selection 
Mode
Monitor Mode Sel
Selects the “U1” monitors displayed on the 4th and 5th lines of the 
digital operator display.
0: 3 Mon Sequential (Displays the next 2 sequential U1 monitors.)
1: 3 Mon Selectable (Displays U1 monitors set by o1-07 and o1-08.)
0 or 1
1**
Programming
115
 Denotes that parameter can be changed when the drive is running.
Parameter
No.
Modbus
Address
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.
Set Value
Description
5
LCD display becomes dark
3
Standard setting
1
LCD display becomes light