6.1 Fault Detection
YASKAWA TM.iQp.01 iQpump Drive User Manual
137
CPF08
WAT-Err
Watchdog Timer Fault
(WAT)
—
Cycle power off and on to the iQpump.
Control circuit damage.
Replace the iQpump.
CPF09
CPU-Err
CPU-ASIC Mutual Diagnosis Fault
(COY)
—
Cycle power off and on to the iQpump.
Control circuit damage.
Replace the iQpump.
CPF10
ASIC-Err
ASIC Version Fault
(ASIC)
Control circuit damage.
Replace the iQpump.
CPF20
Option A/D Error
Option Card Fault
Option card connector connection
fault.
Remove all inputs to the option board.
Option card A/D converter fault.
Perform a factory initialization.
Cycle power off and on to the iQpump.
Replace the option board.
Replace the control board.
CPF21
Option CPU Down
Self-diagnosis Fault of Communication Option
Card
Noise or spike on the
communication line, defective
option board.
Perform a factory initialization.
Cycle power off and on to the iQpump.
Replace the option board.
Replace the control board.
CPF22
Option Type Err
Communication Option Card Code Number Fault Unrecognizable option board is
connected to the control board.
Remove any option boards.
Cycle power off and on to the iQpump.
Perform a factory initialization.
Replace the option board.
Replace the control board.
CPF23
Option DPRAM Err
Communication Option Card Interconnection
Fault
An option board is not correctly
connected to the control board or
an option board that is not made for
the iQpump is attached to the
control board.
Remove power to the iQpump.
Connect the option board once more.
Perform a factory initialization.
Cycle power off and on to the iQpump.
Replace the option board.
Replace the control board.
EF0
Opt External Flt
Communication Option Card External Fault
An external fault condition exists.
Check for an external condition.
Verify the parameters.
Verify communication signal.
EF3
Ext Fault S3
External Fault at Terminal S3
An external fault condition exists
connected to a multi-function
digital input.
Eliminate the cause of an external fault
condition.
EF4
Ext Fault S4
External Fault at Terminal S4
EF5
Ext Fault S5
External Fault at Terminal S5
EF6
Ext Fault S6
External Fault at Terminal S6
EF7
Ext Fault S7
External Fault at Terminal S7
Remove the fault from a multi-function
digital input.
FBL
Feedback Loss
PI Feedback Loss
This fault occurs when PI Feedback Loss
Detection is programmed to fault (b5-12 = 2) and
the PI Feedback < PI Feedback Loss Detection
Level (b5-13) for the PI Feedback Loss Detection
Time (b5-14).
PI Feedback source (e.g.
transducer, sensor, building
automation signal) is not installed
correctly or is not working.
Verify iQpump is programmed to receive
the PI Feedback source signal.
Check to ensure the PI Feedback source
is installed and working properly.
GF
Ground Fault
Output Ground Fault
iQpump output grounding current has exceeded
50% of the iQpump rated output current.
Motor lead is shorted to ground,
DCCT defective.
Remove the motor and run the iQpump
without the motor.
Check the motor for a phase-to-ground
short.
Check the output current with a clamp
on meter to verify the DCCT reading.
Digital
Operator Display
Description
Cause
Corrective Action