5.4 T1 Auto-Tuning

134

YASKAWA TM.iQp.01 iQpump Drive User Manual

5.4

T1 Auto-Tuning

T1-02 Motor Rated Power

Setting Range:

0.00 to 650.00 kW

Factory Default: Model Dependent

T1-04 Motor Rated Current

Setting Range:

Model Dependent

Factory Default: Model Dependent

Auto tuning is recommended to achieve optimum performance. In addition, the iQpump drive requires Line-To-Line Resistance auto-
tuning before it can properly perform the Estimated Speed Search method. This method of speed search allows for bi-directional speed

search. The T1 parameters are found under the Auto-Tuning menu.

To perform auto-tuning follow these steps:

1. T1-02 should be left at the default value (the last 3 digits of the iQpump drive model number).

2. In T1-04, enter the Full Load Amps (FLA) as stamped on the motor’s nameplate.
3. Press the INCREASE key once to display this:

4. If ready, press the HAND key once to start auto-tuning. This process will last for approximately 15 seconds. Once auto-tuning is

finished, the digital operator will display this:

5. To exit the Auto-Tuning menu, press the MENU key once.

Note: It is possible to a get a “Data Invalid” error if the either T1-02 or T1-04 fall outside the range of what the iQpump drive

will accept as reasonable levels for the programmed size of iQpump drive (o2-04).

-ATUNE-

Rdy

Auto-Tuning

0Hz/ 0.00A

Tuning Ready ?

Press RUN key

Press HAND key

-ATUNE-

Tune Successful

0Hz/ 0.00A