beautypg.com

Related parameters – Yaskawa iQpump Drive User Manual User Manual

Page 210

background image

D.1 Using Modbus Communication

210

YASKAWA

TM.iQp.01 iQpump Drive User Manual

Related Parameters

Table D.2 Serial Communication Related Parameters

Modbus communication can perform the following operations regardless of the settings in b1-01 and b1-02:

1. Monitoring operation status of the iQpump drive.
2. Setting and reading iQpump drive parameters.

3. Resetting faults.

4. Input multi-function commands.
IMPORTANT: An OR operation is performed between the multi-function command input from the DDC and the command input from

multi-function digital input terminals S3 to S7.

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

b1-01

0180H

Frequency Reference
Selection
Reference Source

Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

0

Pump Quick

Setup

b1-02

0181H

Run Command Selection
Run Source

Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

0

Pump Quick

Setup

H5-01

0425H

Drive Node Address
Serial Com Adr

Selects Drive station node number (address) for terminals R+, R-, S+,
S-.*
Note:

An address of “0” disables serial com.

0 to 20

(H5-08=0)

0 to FF

(H5-08=1)

0 to 63

(H5-08=2)

1F

Programming

H5-02

0426H

Communication Speed
Selection
Serial Baud Rate

Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud

0 to 4

3

Programming

H5-03

0427H

Communication Parity
Selection
Serial Com Sel

Selects the communication parity for terminals R+, R-, S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

0

Programming

H5-04

0428H

Stopping Method after
Communication Error
Serial Fault Sel

Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

Programming

H5-05

0429H

Communication Error
Detection Selection
Serial Flt Dtct

Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than the time
specified in parameter H5-09, a communications fault will occur.

0 or 1

1

Programming

H5-06

042AH

Drive Transmit Wait
Time
Transmit WaitTIM

Sets the time from when the Drive receives data to when the Drive
sends data.

5 to 65

5 ms

Programming

H5-07

042BH

RTS Control Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 or 1

1

Programming

H5-09

0435H

Communication Error
Detection Time
CE Detect Time

Determines how long communications must be lost before a fault is
annunciated. Works in conjunction with parameters H5-05 and H5-04.

0.0 to 10.0
(H5-08=0)
0.0 to 10.0
(H5-08=1)
0.0 to 90.0
(H5-08=2)

2.0 sec

Programming

 Denotes that parameter can be changed when the iQpump drive is running.
* After these parameters are changed, iQpump drive power must be cycled before the changes will take effect.
# Hex, see

page A-30

.