6.3 Alarm Detection

144

YASKAWA TM.iQp.01 iQpump Drive User Manual

LL3

Loss of Load Det 1

(Flashing)

Loss of Load Detection 1

iQpump output current < L6-02 for more than the

time set in L6-03.

Motor is underloaded.

Ensure the values in L6-02 and
L6-03 are appropriate.
Check application/machine status
to eliminate fault.

OH

Heatsnk Overtemp

(Flashing)

Cooling Fin/Cooling Fin Fan Overheat

The temperature of the iQpump cooling fin
exceeded the temperature programmed in

parameter L8-02.

Cooling fan(s) are not working, high
ambient temperature, a heating unit in
close proximity to iQpump is present.

Check for dirt build-up on the fans

and cooling fins.
Reduce the ambient temperature
around the iQpump.

iQpump Internal Cooling Fan.

Remove the heating unit.

OH2

Over Heat 2

(Flashing)

iQpump overheat pre-alarm signal is input from a
multi-function digital input terminal.

An external overheat condition exists

connected to one of the multi-function
input terminals S3, S4, S5, S6 or S7.

Check for an external condition.
Verify the program parameters
H1-01 thru H1-05.

OH3

Motor Overheat 1

(Flashing)

Motor Overheating Alarm

The iQpump stops or continues operation

according to the setting of L1-03.

Overheating of motor.

Recheck the cycle time and the

size of the load.
Recheck the accel/decel time (C1-
01 to C1-06).
Recheck the V/F pattern (E1-01
thru E1-13).
Recheck the motor rated current

value (E2-01).
Check the digital operator
connector.
Verify the setting of o2-06.

OV

DC Bus Overvolt

(Flashing)

DC Bus Overvoltage

208-240 VAC: Trip point is

≥ 400 Vdc.

480 VAC: Trip point is

≥ 800 Vdc.

High input voltage at R/L1, S/L2 and
T/L3.

Check the input circuit and reduce
the input power to within

specifications.
Extend the time in C1-02, C1-04,
or C1-06.

The deceleration time is set too short.

Power factor correction capacitors are
being used on the input to the
iQpump.

Remove the power factor

correction capacitors.

PRHT

Motor Preheating

Motor Preheating

Motor is preheating.

Motor Preheat 2 input is closed.

UV

DC Bus Undervolt

(Flashing)

DC Bus Undervoltage

The DC bus voltage is

≤ L2-05.

208-240 VAC: Trip point is

≤ 190 Vdc.

480 VAC: Trip point is

≤ 380 Vdc.

Low input voltage at R/L1, S/L2 and
T/L3.

Check the input circuit and
increase the input power to within

specifications.

The acceleration time is set too short. Extend the time in C1-01,

C1-03, or C1-05.

Voltage fluctuation of the input power
is too large.

Check the input voltage.

UV2

CTL PS Undervolt

Control Power Supply Undervoltage of the control
circuit when running.

External load connected pulling down
the iQpump power supplies.

Cycle power off and on to the

iQpump.
Repair or replace the Power PCB/
Gate iQpump PCB.

UV3

MC Answerback

Soft Charge Circuit Fault

The pre-charge contactor opened while the iQpump
was running.

Contacts on the soft charge contactor

are dirty and the soft charge contactor
does not function mechanically.

Cycle power off and on to the
iQpump.
Check the condition of the soft

charge contactor.

Digital

Operator Display

Description

Cause

Corrective Action