4.9 Basic Pump Protection

YASKAWA TM.iQp.01 iQpump Drive User Manual

85

.

Figure 4.9 Not Maintaining Setpoint (NMS) Fault Display

Figure 4.10

Example: Constant Pressure System
System Units set to PSI (P1-02 = PSI)

System Setpoint set for 80 PSI

Pressure Transducer: 150 PSI

Desired Operation:

Pump System should shutdown when the difference between the actual system pressure (transducer feedback level) and the system

setpoint (80 PSI) is greater than 10 PSI continuously for more than 40 sec.

Solution:

Program P1-11 to 10 PSI

Program P1-12 to 40 sec.
The Pump Protection function is only active during running while operating in auto mode. On fault, the iQpump drive will coast to a stop.

-

DRIVE-

RDY

U1-04 =
U2-05 =

0.00 Hz
0.00 A

Setpoint Not Met

NMS

TIME

Not Maintaining
Setpoint (NMS) Fault

Not Maintaining
Setpoint Time P1-12

P1-11

P1-11

SETPOINT

PRESSURE
FEEDBACK