6.4 Operator Programming Errors (OPE)

146

YASKAWA TM.iQp.01 iQpump Drive User Manual

6.4

Operator Programming Errors (OPE)

An Operator Programming Error (OPE) occurs when an inapplicable parameter is set or an individual parameter setting is inappropriate.

The iQpump drive does not operate until the parameter is set correctly. (Alarm output and fault contact do not operate.)

If an OPE occurs, change the appropriate parameter by checking the cause shown in

Table 6.4

.

Table 6.4 OPE Error and Fault Displays

Digital Operator

Display

Description

Cause

Corrective

Action

OPE01

kVA Selection

Drive kVA setting error.

The control board was replaced and the

kVA parameter is set incorrectly.

Enter the correct kVA setting (o2-04) by
referring to the iQpump drive model
number in

Appendix B.

OPE02

Limit

Parameter data out of range.

Parameter set above the allowable range. Verify the program settings.

OPE03

Terminal

Multi-function input selection fault.

Duplicate functions are selected. Speed

search from maximum frequency and set
frequency are set simultaneously. MOP
Increase (H1-0X = 10) and MOP

Decrease (H1-0X = 11) are not set
simultaneously.

Verify program settings.

(H1-01~H1-05)

OPE05

Sequence Select

Run command is selected through serial
communication at 2CN but option board
is not installed.

Serial communication option board is

not installed, option board is installed
incorrectly. The run command selection
parameter.

b1-02 is set to 3 and option board is not

installed.

Verify that the board is installed. Remove
power to the iQpump drive and connect
the option board once more.

OPE10

V/f Ptrn Setting

V/f data setting fault

V/f parameter settings are not set

correctly.

Check parameters (E1-04 ~ E1-11). A
minimum frequency/voltage value may be

set higher than the maximum frequency/
voltage.

OPE11

CarrFrq/On-Delay

Carrier frequency data setting fault.

Carrier frequency proportional gain C6-

05 > 6 and C6-04 > C6-03. Upper/lower
limit error of C6-03 to 5.0kHz.

Parameter setting incorrect.

Check the program settings and correct
the errors.

ERR

EEPROM R/W Err

It does not match at EEPROM write.

• Power supply is turned OFF.

• Parameter is reset repeatedly.

• Cycle power off and on to iQpump.

• Do a factory initialization (A1-03).