C1-11
020AH
Accel/Decel Switch 
Frequency
Acc/Dec SW Freq
Sets the frequency for automatic switching of accel / decel times.
Fout < C1-11: Accel/Decel Time 2
Fout >= C1-11: Accel/Decel Time 1
Multi-function input “Multi-Acc/Dec 1" has priority over C1-11.
0.0 to 
200.0
0.0 Hz
Programming
30
S-Curve Acc/Dec
C2-01
020BH
S-Curve Characteristic at 
Accel Start
SCrv Acc @ Star
t
0.00 to
2.50
0.20 sec Programming
32
C2-02
020CH
S-Curve Characteristic at 
Accel End
SCrv Acc @ End
0.00 to
2.50
0.20 sec Programming
32
Torque Comp
C4-01
0215H
Torque Compensation 
Gain
Torq Comp Gain
This parameter helps to produce better starting torque. It determines 
the amount of torque or voltage boost based upon motor current and 
motor resistance.
0.00 to
2.50
1.00
Programming
33
C4-02
0216H
Torque Compensation 
Primary Delay Time
Torq Comp Time
This parameter adjusts a filter on the output of the torque compensation 
function. Increase to add torque stability, decrease to improve torque 
response.
0 to 10000
200 ms Programming
33
 Denotes that parameter can be changed when the drive is running.
Carrier Freq
C6-01
0223H
Normal Duty Selection
Normal Duty Sel
1: Normal Duty 1
2: Normal Duty 2
1 or 2
2
Programming
34
C6-02
0224H
Carrier Frequency 
Selection
CarrierFreq Sel
Carrier frequency sets the number of pulses per second of the output 
voltage waveform.
0: Low Noise (Carrier frequency is randomly moduled for lower 
audible noise)
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
F: Program (Determined by the settings of C6-03 thru C6-05)
0 to F
kVA
Dependent
Programming
34
C6-03
0225H
Carrier Frequency Upper 
Limit
CarrierFreq Max
Maximum carrier frequency allowed when C6-02 = F.
0.4 to 15.0
kHz
kVA
Dependent
Programming
34
C6-04
0226H
Carrier Frequency Lower 
Limit 
CarrierFreq Min
Minimum carrier frequency allowed when C6-02 = F.
0.4 to 15.0
kHz
kVA
Dependent
Programming
34
C6-05
0227H
Carrier Frequency 
Proportional Gain
CarrierFreq Gain
Sets the relationship of output frequency to carrier frequency when C6-
02 = F.
0 to 99
0
Programming
34
Parameter
No.
Modbus
Address
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.
Time
Run 
command
Output frequency
ON
C2-02
C2-01
OFF
S-curve is used to further soften the starting ramp. 
The longer the S-curve time, the softer the starting 
ramp.