TM.iQp.01 iQpump Drive User Manual

179

L3-04

0492H

Stall Prevention
Selection During Decel
StallP Decel Sel

0: Disabled (The Drive decelerates at the active deceleration rate, C1-
02 or C1-04. If the load is too large or the deceleration time is too short,
an OV fault may occur.)
1: General Purpose (The Drive decelerates at the active deceleration
rate, C1-02 or C1-04, but if the main circuit DC bus voltage reaches the
stall prevention level the output frequency will clamp. Deceleration
will continue once the DC bus level drops below the stall prevention
level.)
2: Intelligent (The active deceleration rate is ignored and the Drive
decelerates as fast as possible w/o hitting OV fault level.)

0 to 3

1

Programming

102

L3-05

0493H

Stall Prevention Level
During Decel
StallP Run Sel

0: Disabled (Drive runs a set frequency.) A heavy load may cause the
Drive to trip on an OC fault.
1: Decel Time 1 (In order to avoid stalling during heavy loading, the
Drive will start to decelerate at Decel time 1 (C1-02) if the output
current exceeds the level set by L3-06. Once the current level drops
below the L3-06 level the Drive will accelerate back to its set
frequency at the active acceleration rate.)
2: Decel Time 2 (Same as setting 1 except the Drive decelerates at
Decel Time 2 (C1-04).) For 6 Hz or less frequency, stall prevention
function during run is disabled regardless of L3-05 set.

0 to 2

1

Programming

103

L3-06

0494H

Stall Prevention Level
During Running
StallP Run Level

This function is enabled when L3-05 is “1” or “2”.
Drive rated current is set as 100%.
Normally, changing the setting is not required.
Decrease the set value if stalling occurs at factory setting.

30 to 200

120%

Programming

103

Ref Detection

L4-01

0499H

Speed Agreement
Detection Level
Spd Agree Level

L4-01 and L4-02 are used in conjunction with the multi-function
outputs, (H2-01and H2-02) as a setpoint and hysteresis for a contact
closure.

0.0 to
200.0

0.0 Hz

Programming

104

L4-02

049AH

Speed Agreement
Detection Width
Spd Agree Width

0.0 to 20.0

2.0 Hz

Programming

104

L4-05

049DH

Frequency Reference
Loss Detection Selection
Ref Loss Sel

Determines how the Drive will react when the frequency reference is
lost.
0: Stop (Disabled) - Drive will not run at the frequency reference.
1: Enabled @ % of PrevRef - Drive will run at a percentage (L4-06) of
the frequency reference level at the time frequency reference was lost.

Note:

Only available in the Hand Mode (P5-01 = 0).

0 or 1

0

Programming

105

L4-06

04C2H

Frequency Reference
Level at Loss Frequency
Fref at Floss

If Frequency Reference loss function is enabled (L4-05 = 1) and
Frequency Reference is lost, then the Drive will run at reduced
frequency reference determined by L4-06. New Fref=Fref at time of
loss x L4-06.

Note:

Only available in the Hand Mode (P5-01 = 0)

0 or 1

0

Programming

105

Fault Restart

L5-01

049EH

Number of Auto Restart
Attempts
Num of Restarts

Determines the number of times the Drive will perform an automatic
restart.

0 to 10

0

Pump Quick

Setup

105

L5-02

049FH

Auto Restart Operation
Selection
Restart Sel

Determines if the fault contact activates during an automatic restart
attempt.
0: No Flt Relay - fault contact will not activate during an automatic
restart.
1: Flt Relay Active - fault contact will activate during an automatic
restart.

0 or 1

0

Programming

105

L5-03

04A0H

Maximum Restart Time
After Fault
Max Restart Time

If the restart fails (or is not attempted due to a continuing fault
condition, e.g. an OV fault) the Drive waits the Maximum Restart Time
After Fault (L5-03) before attempting another restart. This parameter is
not applicable to Loss of Prime Fault.

10.0 to
3600.0

<0032>

180.0 sec

Pump Quick

Setup

105

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.