5 auto-tuning faults, Auto-tuning faults – Yaskawa iQpump Drive User Manual User Manual
Page 147

6.5 Auto-Tuning Faults
YASKAWA TM.iQp.01 iQpump Drive User Manual
147
6.5
Auto-Tuning Faults
Auto-tuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator and the motor
coasts to a stop during operation. The fault contact is not activated.
Table 6.5 Auto-Tuning Displays and Processing
Digital Operator Display
Probable Cause
Corrective Action
Er - 01
Fault
• There is an error in the data input for autotuning.
• There is an error in the relationship between the motor
output and the motor rated current.
• Check input data.
• Check iQpump and motor capacity.
• Check motor rated current.
Er - 02
Minor Fault
A minor fault is detected during auto-tuning.
• Check input data.
• Check wirings and around the machine.
• Check the load.
Er - 03
STOP key
The STOP key is pressed during auto-tuning, and the auto-
tuning is interrupted.
—
Er - 04
Resistance
Auto-tuning is not completed within the specified time.
The auto-tuning result became other than the parameter set
range.
• Check input data.
• Check motor wiring.
• If a motor and a machine are connected, disconnect the
motor from the machine.
Er - 12
I-det. Circuit
• Current flow exceeded the motor rated current.
• Current detection value symbol was reversed.
• Any of U/TI, V/T2, and W/T3 has open-phase.
• Check current detection circuit, wiring and mounting
procedure.
Er - 13
Leakage Inductance Fault
Auto-tuning did not finish within the set time.
Tuning result was outside the acceptable parameter setting
range.
• Check motor wiring.
End - 3
Data Invalid
Rated current set value is set too high.
• Check input data (especially, motor output current and
motor rated current value).