480 vac, C.1 standard iqpump drive specifications – Yaskawa iQpump Drive User Manual User Manual
Page 205

C.1 Standard iQpump Drive Specifications
YASKAWA
TM.iQp.01 iQpump Drive User Manual
205
◆ 480 VAC
Table C.2 480 VAC iQpump Drive Specifications
Table C.2 480 VAC iQpump Drive Specifications (Continued)
Model Number CIMR-P7U-107
40P4
40P7
41P5
42P2
43P7
45P5
47P5
49P0
4011
4015
4018
O
u
tput
Ratin
g
s
Rated output capacity (kVA)
1.4
1.6
2.8
4.0
5.8
9.5
13.0
16.0
21.0
26.0
30.0
Motor HP (460V)
0.5/0.75
1
1.5/2
3
5
7.5
10
15
20
25
30
Rated output current (A)
1.8
2.1
3.7
5.3
7.6
12.5
17.0
21.0
27.0
34.0
40.0
Max. output voltage (V)
3-phase; 380, 400, 415, 440, 460, or 480 VAC (Proportional to input voltage.)
Max. output frequency (Hz)
120 Hz
Pow
e
r Supp
ly
Char
acte
ri
s
ti
cs
Rated voltage (V)
Rated frequency (Hz)
3-phase, 380, 400, 415, 440, 460 or 480 VAC, 50/60 Hz
Rated input current (A)
2.2
2.5
4.4
6.4
9.0
15
20
26
33
40
48
Allowable voltage fluctuation
+ 10%, - 15%
Allowable frequency fluctuation
±5%
Control
Char
act
er
ist
ics
Measures for
power supply
harmonics
DC Reactor
Optional
12-pulse
Rectification
Not possible
Model Number CIMR-P7U-107
4024
4030
4037
4045
4055
4075
4090
4110
4160
4185
4220
4300
O
u
tput
Ra
ti
ng
s
Rated output capacity (kVA)
40.0
51.0
59.0
73.0
95.0
120.0
140.0
180.0
230.0
315.0
390.0
510.0
Motor HP (460V)
40
50
60
75
100
125
150
200
250
300/350
400/450
500+
Rated output current (A)
52.0
67.2
77.0
96.0
125.0
156.0
180.0
240.0
304.0
414.0
515.0
675.0
Max. output voltage (V)
3-phase, 380, 400, 415, 440, 460 or 480 VAC (Proportional to input voltage)
Max. output frequency (Hz)
120 Hz
Pow
er
Suppl
y
C
h
ar
a
ct
e
ri
st
ic
s
Max. voltage (V)
Rated frequency (Hz)
3-phase, 380, 400, 415, 440, 460, or 480 VAC, 50/60 Hz
Rated input current (A)
57
74
85
106
134
172
198
264
334
456
567
743
Allowable voltage fluctuation
+ 10%, - 15%
Allowable frequency fluctuation
±5%
Control
Char
act
eri
s
ti
cs
Measures for power
supply harmonics
DC Reactor
Built-in
12-Pulse
Rectification
Possible
Note:
The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and Drive, be sure that the Drive's rated output current is
applicable for the motor's rated current.
A 3-wire phase-shifting transformer is required on the power supply for 12-pulse rectification.