SMA SC 500CP-US-10 600V User Manual
Page 99

SMA America, LLC
13 Parameters
Operating Manual
SCCP-US-BE-US_en-52
99
Q-VLockInTm**
Waiting time for
activating the Q(V)
characteristic curve
0 s to 100 s
‒
2 s
Waiting time for
deactivating the Q(V)
characteristic curve
0 s to 100 s
‒
2 s
Q-VArGraNomPos
**
Reactive power gradient
at a positive voltage
change of the nominal
voltage
0%/V to 40.06%/V
SC 500CP-US-10
0%/V
0%/V to 54.15%/V
SC 500CP-US-10 600V
0%/V to 31.47%/V
SC 630CP-US-10
0%/V to 27.82%/V
SC 720CP-US-10
0%/V to 26.70%/V
SC 750CP-US-10
0%/V to 25.04%/V
SC 800CP-US-10
0%/V to 23.56%/V
SC 850CP-US-10
0%/V to 22.25%/V
SC 900CP-US-10
Q-VArGraNomNeg
Reactive power gradient
at a negative voltage
change of the nominal
voltage
0%/V to 40.06%/V
SC 500CP-US-10
0%/V
0%/V to 54.15%/V
SC 500CP-US-10 600V
0%/V to 31.47%/V
SC 630CP-US-10
0%/V to 27.82%/V
SC 720CP-US-10
0%/V to 26.70%/V
SC 750CP-US-10
0%/V to 25.04%/V
SC 800CP-US-10
0%/V to 23.56%/V
SC 850CP-US-10
0%/V to 22.25%/V
SC 900CP-US-10
PF-PFSubValRun
Replacement value cos φ
for normal feed-in
operation during
communication
disturbance
0.9 to 1
‒
1
PF-PFExtSubValR
Replacement value of the
excitation type for normal
feed-in operation during
communication
disturbance
OvExt
Overexcited
OvExt
UnExt
Underexcited
PwrMonErrMod
Procedure used during
communication
disturbance
LastVal
Use of last default values
received
LastVal
SubVal
Use of replacement
values
Name
Description
Value/range
Explanation
Default
value