8  Reactive Power Control

SMA America, LLC

64

SCCP-US-BE-US_en-52

Operating Manual

In order to prevent several systems with this function from influencing each other, the Q-VArTmsVtg parameter can be

used to set a delay time. This delay time indicates for how long a voltage change must be pending before a change in

the reactive power supply results. This allows several systems to alternately control the line voltage at the grid connection

joint.
The Q-EnaTmsVtg parameter can be used to switch the delay time on and off.

8.2 Displaying Error Messages and Warnings for the Reactive Power

Setpoint

The instantaneous value Q-VArModFailStt displays errors or warnings relating to the reactive power setpoint.

Procedure: Display the instantaneous value Q-VArModFailStt on the user interface (see Section 6.1 "Displaying

Instantaneous Values", page 51).

Parameters used

Q-VolWidNom
Q-VolNomP1
Q-VolNomP2
Q-VArGraNom
Q-VArTmsSpnt
Q-VArTmsVtg
Q-EnaTmsVtg

Display

Cause and corrective measures

Off

No procedure for specifying the reactive power setpoint has been selected.

Ok

A procedure for specifying the reactive power setpoint has been selected and there are no errors.

ComFail

The VArCtlCom or PFCtlCom procedure has been chosen and the expected signal with a valid

reactive power setpoint has been absent for at least five minutes.

Corrective measures:

• Ensure that the inverter and the Power Plant Controller can be accessed via the Internet.
• Ensure that the inverter and the Power Plant Controller are connected correctly.
• Ensure that the cabling between the inverter and Power Plant Controller is OK.

AnInFail

The VArCnstNomAnIn or PFCnstNomAnIn procedure has been chosen and the value

measured at the analog input is less than 2 mA.

Corrective measures:

• Make sure the signal cable is correctly connected to the analog input.

ComInvalid

The VArCtlCom or PFCtlCom procedure has been chosen and the information on the power

specification settings contains invalid content.

Corrective measures:

• Check the power specification settings.