SMA SC 500CP-US-10 600V User Manual
Page 107

SMA America, LLC
13 Parameters
Operating Manual
SCCP-US-BE-US_en-52
107
TmZn
Time zone
GMT − 12:00 to
GMT +12:00
Time zone setting
Country-s
pecific
ExtSolIrrOfs
Offset of the external irradiation
sensor
− 5,000 to +5,000 ‒
0
ExtSolIrrGain
Amplification of the external
irradiation sensor
− 1,000 to +1,000 ‒
1
Resets meter
h-Cnt
Operating hours meter
‒
E-Cnt
Energy meter
CntFanHs
All fan runtime meters
CntFanCab1
Fan runtime meter
CntFanCab2
Fan runtime meter
CntHtCab2
Fan runtime meter
Offset for operating hours
0 h to 2,147,482 h ‒
0
Ofs_h-Total**
Offset for feed-in hours
0 h to 2,147,482 h ‒
0
Offset for total supplied energy
0 kWh to
214,748,367 kWh
‒
0
Ofs_CntFanHs*
Offset for operating hours of
heat sink fan
0 h to 2,147,482 h ‒
0
Ofs_CntFanCab1* Offset for operating hours of
internal fan 1
0 h to 2,147,482 h ‒
0
Ofs_CntFanCab2* Offset for operating hours of
internal fan 2
0 h to 2,147,482 h ‒
0
Ofs_CntHtCab2*
Offset for operating hours of
internal heater 2
0 h to 2,147,482 h ‒
0
SpntRemEna
Enables the plant remotely
Stop
Deactivated
Run
Run
Activated
Ackn
Acknowledges errors in inverter
Ackn
Selects parameter to
acknowledge an error
-
GdErrTm**
Waiting time for grid error
0 s to 600 s
‒
300 s
ExlStrStpEna*
Activation of the external
shutdown signal / remote
shutdown
Off
Deactivated
Off
On
Activated
ExlTrfErrEna*
Activation of the hermetic
protection of the
medium-voltage transformer
Off
Deactivated
On
On
Activated
* These parameters can only be viewed after the installer password has been entered.
** These parameters can only be changed after the installer password has been entered.
Name
Description
Value/range
Explanation
Default
value