7  Active Power Limitation

Operating Manual

SCCP-US-BE-US_en-52

55

7.3 Displaying the Status of the Active Power Limitation

The instantaneous value P-WModStt displays the status of the active power limitation.

Procedure:

• Display the instantaneous value of the P-WModStt channel on the user interface (see Section 6.1 "Displaying

Instantaneous Values", page 51).

7.4 Displaying Error Messages and Warnings of Active Power Limitation

The instantaneous value P-WModFailStt displays the error messages or warnings associated with active power

limitation.

Procedure:

• Display the instantaneous value P-WModFailStt on the user interface (see Section 6.1 "Displaying Instantaneous

Values", page 51).

Display

Description

Off

No procedure for active power limitation has been selected.

WMax

Active power is limited by the specified maximum limit. This limit is based on Pmax.

Hz

Active power is limited by a frequency increase.

Tmp

Active power is limited due to temperature derating.

AmpPv

Active power is limited via a PV current limitation.

AmpAC

The active power is limited via an AC current limitation.

Display

Cause and corrective measures

Off

No procedure for active power limitation has been selected.

Ok

A procedure for active power limitation has been selected and there are no errors.

ComFail

The WCtlCom procedure has been chosen and the expected signal with a valid active power limitation

has been absent for at least five minutes.

Corrective measures:

• Ensure that the inverter and the Power Plant Controller can be accessed via the Internet.
• Ensure that the inverter and the Power Plant Controller are connected correctly.
• Ensure that the cabling between the inverter and Power Plant Controller is OK.

AnInFail

The WCnstNomAnIn procedure has been chosen and the value measured at the analogue input is less

than 2 mA.

Corrective measures:

• Make sure the signal cable is correctly connected to the analog input.

ComInvalid The WCtlCom procedure has been chosen and the information about the specified power output

contains invalid content.
Corrective measures:

• Check the power specification settings.