11  Troubleshooting

Operating Manual

SCCP-US-BE-US_en-52

81

11.4.3 Error Number 34xx to 40xx ‒ Disturbance on the PV Array

1301

Left rotating magnetic field is connected.

30 s

A

• Check phase position.
• Make sure all fuses are switched

on.

1500

The grid engagement conditions are not

achieved again after a grid error.

W

W

• Check power frequency and line

voltage.

* Depending on the parameterization, the error message must be acknowledged manually.

Error no.

Explanation

Behavior of the

inverter

Corrective measures

S 1

S 2

R

3403

The voltage of the PV generator is too high. 15 min 30 min

• Check the DC input voltage.
• Check the module wiring and

plant design.

3404

Open-circuit voltage is too high. Fault

detected by standard monitoring.

15 min 30 min

3406

The active power is too high due to the

electrical voltage of the PV generator

being too high.

15 min 30 min

3501

The insulation monitoring device has

measured an excessively low insulation

resistance.
For the options "GFDI and insulation

monitoring device" and "Advanced

Remote GFDI and insulation monitoring

device", the insulation monitoring device is

only active when the GFDI or the

Advanced Remote GFDI is open.

C

C

• Check the PV array for

insulation errors.

3502

The GFDI has tripped.

C

C

3504

The insulation monitoring device has

detected an insulation error. Since the

parameter IsoErrIgn is set to On, this error

is ignored.

W

W

3507

A ground fault has occurred on the

ungrounded pole of the PV array.

A

A

3510

The inverter has found an insulation error

on the inverter bridge.

A

A

3511

The Advanced Remote GFDI has detected

a temporary ground fault.

3512

The Advanced Remote GFDI has detected

a permanent ground fault.

A

A

3517

Insulation measuring will be performed.

W

W

Error no.

Explanation

Behavior of the

inverter

Corrective measures

S 1

S 2

R