13 Parameters
Operating Manual
SCCP-US-BE-US_en-52
105
13.1.4 Insulation Monitoring
Line-to-line voltage on the
undervoltage side of the
external transformer
1 V to 500 V
SC 500CP-US-10
270 V
SC 500CP-US-10 600V
200 V
SC 630CP-US-10
315 V
SC 720CP-US-10
324 V
SC 750CP-US-10
342 V
SC 800CP-US-10
360 V
SC 850CP-US-10
386 V
SC 900CP-US-10
405 V
* These parameters can only be changed after the installer password has been entered.
Name
Description
Value/range
Explanation
Default
value
IsoErrIgn*
Enables insulation error
detection
Off
Deactivated
On
On
Activated
RemMntSvc
PV array grounding will be
removed.
Off
Plant maintenance off
Off
On
Plant maintenance on
IsoSmidOutGrp
Procedure for the correction of
insulation errors.
Auto
Automatic insulation
measuring
Auto
Man
Manual insulation
measuring
Start
Start of the isolation of
the strings for insulation
measuring
RisoCtlWarn
Alert threshold for the insulation
monitoring device iso-PV1685
0 kΩ to 50 kΩ
‒
45 kΩ
PvVtgRisoStart
Start voltage of the insulation
measuring
0 V to 1,200 V
SC 500CP-US-10
500 V
SC 500CP-US-10 600V
390 V
SC 630CP-US-10
610 V
SC 720CP-US-10
675 V
SC 750CP-US-10
715 V
SC 800CP-US-10
760 V
SC 850CP-US-10
760 V
SC 900CP-US-10
770 V
PvVtgRisoDif
Difference voltage to
PvVtgStrLevMin for changing
from insulation measuring into
feed-in operation
− 250 V to +250 V ‒
0 V
IsoDev*
Selection of the insulation
monitoring device
isoPV3
‒
isoPV1685
isoPV1685
‒
Name
Description
Value/range
Explanation
Default
value