SMA America, LLC

13  Parameters

Operating Manual

SCCP-US-BE-US_en-52

105

13.1.4 Insulation Monitoring

TrfVolExlLo*

Line-to-line voltage on the

undervoltage side of the

external transformer

1 V to 500 V

SC 500CP-US-10

270 V

SC 500CP-US-10 600V

200 V

SC 630CP-US-10

315 V

SC 720CP-US-10

324 V

SC 750CP-US-10

342 V

SC 800CP-US-10

360 V

SC 850CP-US-10

386 V

SC 900CP-US-10

405 V

* These parameters can only be changed after the installer password has been entered.

Name

Description

Value/range

Explanation

Default

value

IsoErrIgn*

Enables insulation error

detection

Off

Deactivated

On

On

Activated

RemMntSvc

PV array grounding will be

removed.

Off

Plant maintenance off

Off

On

Plant maintenance on

IsoSmidOutGrp

Procedure for the correction of

insulation errors.

Auto

Automatic insulation

measuring

Auto

Man

Manual insulation

measuring

Start

Start of the isolation of

the strings for insulation

measuring

RisoCtlWarn

Alert threshold for the insulation

monitoring device iso-PV1685

0 kΩ to 50 kΩ

45 kΩ

PvVtgRisoStart

Start voltage of the insulation

measuring

0 V to 1,200 V

SC 500CP-US-10

500 V

SC 500CP-US-10 600V

390 V

SC 630CP-US-10

610 V

SC 720CP-US-10

675 V

SC 750CP-US-10

715 V

SC 800CP-US-10

760 V

SC 850CP-US-10

760 V

SC 900CP-US-10

770 V

PvVtgRisoDif

Difference voltage to

PvVtgStrLevMin for changing

from insulation measuring into

feed-in operation

− 250 V to +250 V ‒

0 V

IsoDev*

Selection of the insulation

monitoring device

isoPV3

isoPV1685

isoPV1685

Name

Description

Value/range

Explanation

Default

value