2 grid monitoring/grid limits – SMA SC 500CP-US-10 600V User Manual
Page 101

SMA America, LLC
13 Parameters
Operating Manual
SCCP-US-BE-US_en-52
101
13.1.2 Grid Monitoring/Grid Limits
UL listing
The default limiting values for the line voltage and the power frequency are configured in accordance with
IEEE 1547, as required for UL1741 certification. The parameters for these limiting values are marked with ** in this
section. These parameters may only be changed by authorized personnel at the written direction of the utility. The
inverter can be operated outside the IEEE 1547 limits when required by the utility without loss of UL certification.
• Do not make any changes to the default limiting values for the grid monitoring parameters unless directed by
the utility.
• Inverter capability range shown in {brackets}
• 50 Hz values shown in [brackets]
• Grid monitoring measurement accuracy:
– Voltage measurement: +/– 8.5 V
– Frequency measurement: +/– 0.06 Hz
– Disconnect time: +/–4.5%
Name
Description
Range
Explanation
Default
value
VRtg*
Nominal line voltage of the
electricity grid
1 V to 70,000 V ‒
20,000 V
Limiting value for
overvoltage tripping level 3
100% to 150% ‒
100%
Tripping time at overvoltage
level 3
0 ms to
1,000,000 ms
‒
0 ms
VCtlhhLim**
Limiting value for
overvoltage release level 2
104% to 120% Parameter range specified by
IEEE 1547. Do not operate
outside the standard range
unless directed by the utility.
120%
Tripping time at overvoltage
level 2
0 ms to
1,000,000 ms
Parameter value specified by
IEEE 1547. Do not operate
using a different parameter
value unless directed by the
utility.
160 ms
[200 ms]
Limiting value for
overvoltage release level 1
104% to 116% Parameter range specified by
IEEE 1547. Do not operate
outside the standard range
unless directed by the utility.
110%
VCtlhLimTm**
Tripping time at overvoltage
level 1
0 ms to
1,000,000 ms
Parameter value specified by
IEEE 1547. Do not operate
using a different parameter
value unless directed by the
utility.
1,000 ms
Limiting value for
undervoltage release level 1
54% to 96%
{0% to 100%}
Parameter range specified by
IEEE 1547. Do not operate
outside the standard range
unless directed by the utility.
88%