13  Parameters

Operating Manual

SCCP-US-BE-US_en-52

101

13.1.2 Grid Monitoring/Grid Limits

UL listing
The default limiting values for the line voltage and the power frequency are configured in accordance with

IEEE 1547, as required for UL1741 certification. The parameters for these limiting values are marked with ** in this

section. These parameters may only be changed by authorized personnel at the written direction of the utility. The

inverter can be operated outside the IEEE 1547 limits when required by the utility without loss of UL certification.

• Do not make any changes to the default limiting values for the grid monitoring parameters unless directed by

the utility.

• Inverter capability range shown in {brackets}
• 50 Hz values shown in [brackets]
• Grid monitoring measurement accuracy:

– Voltage measurement: +/– 8.5 V
– Frequency measurement: +/– 0.06 Hz
– Disconnect time: +/–4.5%

Name

Description

Range

Explanation

Default

value

VRtg*

Nominal line voltage of the

electricity grid

1 V to 70,000 V ‒

20,000 V

VCtlMax*

Limiting value for

overvoltage tripping level 3

100% to 150% ‒

100%

VCtlMaxTm*

Tripping time at overvoltage

level 3

0 ms to

1,000,000 ms

0 ms

VCtlhhLim**

Limiting value for

overvoltage release level 2

104% to 120% Parameter range specified by

IEEE 1547. Do not operate

outside the standard range

unless directed by the utility.

120%

VCtlhhLimTm**

Tripping time at overvoltage

level 2

0 ms to

1,000,000 ms

Parameter value specified by

IEEE 1547. Do not operate

using a different parameter

value unless directed by the

utility.

160 ms

[200 ms]

VCtlhLim**

Limiting value for

overvoltage release level 1

104% to 116% Parameter range specified by

IEEE 1547. Do not operate

outside the standard range

unless directed by the utility.

110%

VCtlhLimTm**

Tripping time at overvoltage

level 1

0 ms to

1,000,000 ms

Parameter value specified by

IEEE 1547. Do not operate

using a different parameter

value unless directed by the

utility.

1,000 ms

VCtllLim**

Limiting value for

undervoltage release level 1

54% to 96%

{0% to 100%}

Parameter range specified by

IEEE 1547. Do not operate

outside the standard range

unless directed by the utility.

88%