3 grid support, Vctlmax, Vctlmaxtm – SMA SC 500CP-US-10 600V User Manual

Page 104: Vctlhhlimtm, Vctlhlim, Vctlllim, Vctlllimtm, Vctllllimtm, Vctlmin, Vctlmintm

background image

13  Parameters

SMA America, LLC

104

SCCP-US-BE-US_en-52

Operating Manual

13.1.3 Grid Support

ManResPID

Manual switching on

interruption through PID

Off

Deactivated

Off

On

Activated

ManResPLD

Manual activation after

interruption due to

disturbance in a line

conductor

Off

Deactivated

Off

On

Activated

* These parameters can only be changed after the installer password has been entered.

**

This parameter may only be changed by authorized personnel at the written direction of the utility.

Name

Description

Value/range

Explanation

Default

value

FRTMod**

Dynamic grid support

operating modes

FRT_BDEW

Complete Dynamic

Grid Support

FRT_OFF

FRT_Partial

Limited Dynamic

Grid Support

FRT_SDLWindV

Complete dynamic

grid support with FRT

characteristic curve

FRT_OFF

Deactivation of dynamic

grid support

FRTSwOffTm**

Deactivation delay of the

LVRT

0 ms to 10,000 ms ‒

500 ms

FRTArGraNom*

Scaling of the k-factor for

LVRT

1 to 10

2

FRTDbVolNomMax**

Upper limit of the voltage

deadband

0% to 100%

10%

FRTDbVolNomMin**

Lower limit of the voltage

dead band

− 100% to 0%

− 10%

FRT2ArGraNomHi*

Gradient of the FRT

characteristic curve in the

event of overvoltage in the

operating mode

FRT_SDLWindV

1 to 10

2

FRT2ArGraNomLo*

Gradient of the FRT

characteristic curve in the

event of undervoltage in the

operating mode

FRT_SDLWindV

1 to 10

2

EnaAid*

Enables islanding detection

Off

Deactivated

On

On

Activated

TrfVolExlHi*

Line-to-line voltage on the

overvoltage side of the

external transformer

1 V to 70,000 V

20,000 V

Name

Description

Range

Explanation

Default

value