3 grid support, Vctlmax, Vctlmaxtm – SMA SC 500CP-US-10 600V User Manual
Page 104: Vctlhhlimtm, Vctlhlim, Vctlllim, Vctlllimtm, Vctllllimtm, Vctlmin, Vctlmintm

13 Parameters
SMA America, LLC
104
SCCP-US-BE-US_en-52
Operating Manual
13.1.3 Grid Support
ManResPID
Manual switching on
interruption through PID
Off
Deactivated
Off
On
Activated
ManResPLD
Manual activation after
interruption due to
disturbance in a line
conductor
Off
Deactivated
Off
On
Activated
* These parameters can only be changed after the installer password has been entered.
**
This parameter may only be changed by authorized personnel at the written direction of the utility.
Name
Description
Value/range
Explanation
Default
value
FRTMod**
Dynamic grid support
operating modes
FRT_BDEW
Complete Dynamic
Grid Support
FRT_OFF
FRT_Partial
Limited Dynamic
Grid Support
FRT_SDLWindV
Complete dynamic
grid support with FRT
characteristic curve
FRT_OFF
Deactivation of dynamic
grid support
FRTSwOffTm**
Deactivation delay of the
LVRT
0 ms to 10,000 ms ‒
500 ms
FRTArGraNom*
Scaling of the k-factor for
LVRT
1 to 10
‒
2
FRTDbVolNomMax**
Upper limit of the voltage
deadband
0% to 100%
‒
10%
FRTDbVolNomMin**
Lower limit of the voltage
dead band
− 100% to 0%
‒
− 10%
FRT2ArGraNomHi*
Gradient of the FRT
characteristic curve in the
event of overvoltage in the
operating mode
FRT_SDLWindV
1 to 10
‒
2
FRT2ArGraNomLo*
Gradient of the FRT
characteristic curve in the
event of undervoltage in the
operating mode
FRT_SDLWindV
1 to 10
‒
2
EnaAid*
Enables islanding detection
Off
Deactivated
On
On
Activated
TrfVolExlHi*
Line-to-line voltage on the
overvoltage side of the
external transformer
1 V to 70,000 V
‒
20,000 V
Name
Description
Range
Explanation
Default
value