SMA SC 500CP-US-10 600V User Manual
Page 103

SMA America, LLC
13 Parameters
Operating Manual
SCCP-US-BE-US_en-52
103
HzCtlhLim**
Threshold for overfrequency
level 1
60 Hz to 66 Hz
[50 Hz to 56 Hz]
Parameter value specified by
IEEE 1547. Do not operate
using a different parameter
value unless directed by the
utility.
60.5 Hz
[50.5 Hz]
HzCtlhLimTm**
Tripping time for
overfrequency level 1
0 ms to
1,000,000 ms
Parameter value specified by
IEEE 1547. Do not operate
using a different parameter
value unless directed by the
utility.
160 ms
[200 ms]
HzCtllLim**
Threshold for
underfrequency level 1
57 Hz to
59.8 Hz
[47 Hz to
49.8 Hz]
Parameter value specified by
IEEE 1547. Do not operate
using a different parameter
value unless directed by the
utility.
59.3 Hz
[49.3 Hz]
Tripping time for
underfrequency level 1
160 ms to
300,000 ms
Parameter value specified by
IEEE 1547. Do not operate
using a different parameter
value unless directed by the
utility.
160 ms
[200 ms]
HzCtlllLim**
Threshold for
underfrequency level 2
55 Hz to 60 Hz
[45 Hz to 50 Hz]
Parameter value specified by
IEEE 1547. Do not operate
using a different parameter
value unless directed by the
utility.
57.0 Hz
[47 Hz]
HzCtlllLimTm**
Tripping time for
underfrequency level 2
0 ms to
1,000,000 ms
Parameter value specified by
IEEE 1547. Do not operate
using a different parameter
value unless directed by the
utility.
160 ms
[200 ms]
HzCtlMin*
Threshold for
underfrequency level 3
55 Hz to 60 Hz
[45 Hz to 50 Hz]
‒
55 Hz
[55 Hz]
HzCtlMinTm*
Tripping time for
underfrequency level 3
0 ms to
1,000,000 ms
‒
100 ms
ManResOvrVol
Manual switching on after
overvoltage
Off
Deactivated
Off
On
Activated
ManResUndrVol
Manual switching on after
undervoltage
Off
Deactivated
Off
On
Activated
ManResOvrFrq
Manual switching on after
overfrequency
Off
Deactivated
Off
On
Activated
ManResUndrFrq
Manual switching on after
underfrequency
Off
Deactivated
Off
On
Activated
Name
Description
Range
Explanation
Default
value