1 no q at night: off procedure – SMA SC 500CP-US-10 600V User Manual

Page 66

background image

8  Reactive Power Control

SMA America, LLC

66

SCCP-US-BE-US_en-52

Operating Manual

7. If SubVal has been selected, enter the proxy values for normal feed-in operation and for operation outside of normal

feed-in operation, as follows:

8. In the parameter PwrMonErrTm configure the time lapse until recognition of the absence of setpoint values.
9. Confirm the parameter entry with [Save].

8.3.1.1 No Q at Night: Off Procedure

The reactive power setpoint is limited to 0 kVAr. This setpoint cannot be controlled.

8.3.1.2 Q at Night with Operation Command via Modbus Protocol: WCtlCom Procedure

The SC-COM receives the reactive power setpoint via Modbus and transmits it to the inverter. The setpoint is transmitted

as a percentage and converted to kVAr in the device.
If the inverter has not received any signal for the last five minutes, the error message will be displayed in the instantaneous

value Q-VArModFailStt.

8.3.1.3 Q at Night with Absolute Value: VArCnst Procedure

The reactive power setpoint is set using the parameter QoDQ-VAr. Note that the parameter QoDQ-VAr may be within

the range ‒QoDQmax to +QoDQmax.

8.3.1.4 Q at Night as a Percentage of the Nominal Power: VArCnstNom Procedure

The parameter QoDQ-VArNom is used to set the reactive power setpoint in %. The parameter QoDQ-VArNom refers

to Pmax. If the calculated amount of reactive power exceeds the predefined value of QoDQmax, the power will be

limited to QoDQmax. If the calculated amount of reactive power falls below the predefined value of ‒QoDQmax, the

power will be limited to ‒QoDQmax.

8.3.1.5 Q at Night via Standard Signal: VArCnstNomAnIn Procedure

The reactive power setpoint is set via an analog signal at the input terminals for setpoint specification (see Sunny Central

installation manual). This is usually implemented by a ripple control receiver.
The analog value is converted into a reactive power setpoint. The electrical current strength of the connected signal

determines the setpoint.

SubVal

Utilization of the configured proxy values. SMA recommends use of the proxy values when

setpoint specifications are effected via analog signals.

Parameters

Description

Q-VArSubValRun

Proxy value for the reactive power setpoint in feed-in operation

PF-PFSubValRun

Proxy value for the displacement power factor in feed-in operation

PF-PFExtSubValR

Proxy value for the excitation of the displacement power factor in feed-in operation

Q-VArSubVal

Proxy value for the reactive power setpoint outside of feed-in operation

PF-PFSubVal

Proxy value for the displacement power factor outside of feed-in operation

PF-PFExtSubVal

Proxy value for the excitation of the displacement power factor outside of feed-in operation

Parameters used

none

Parameters used

none

Parameters used

QoDQ-VAr

Parameters used

QoDQ-VArNom