3  Product Description

SMA America, LLC

22

SCCP-US-BE-US_en-52

Operating Manual

3 Product Description

This section will give you an overview of the inverter and its components.

3.1 Plant Overview

The Sunny Central CP-US is a PV inverter which converts the direct current generated in the PV modules into grid-compliant

alternating current. An external MV transformer fitted downstream feeds the alternating current generated into the utility

grid.
An AC Disconnect and DC Disconnect must be installed in accordance with NEC ANSI/NFPA 70 and CEC.
The inverter can be optionally ordered with an integrated AC Disconnect and an integrated DC Switch. Both devices are

designed to be used with a lockout device to secure the inverter against reconnection during service. With the AC

Disconnect, the inverter can be disconnected from the utility grid simply and safely. This option does not require an

additional AC Disconnect Unit on the AC side.
With the DC Switch, the inverter can be disconnected from the PV array. If the inverter does not have an integrated DC
Switch, an external DC Disconnect must be installed in accordance with NEC ANSI/NFPA 70 and CEC, in order to be
able to disconnect the inverter from the PV array. This allows you to easily and safely disconnect the inverter as needed.
In some jurisdictions, additional external disconnecting means may be required for servicing of the DC input fuses. SMA
recommends an early review with the AHJ to identify their requirements for the PV System.

Sunny Central Inverter with Integrated AC Disconnect and Integrated DC Switch

Figure 3: Principle of a grid-connected PV plant with a Sunny Central inverter with integrated AC Disconnect and DC Switch

Position

Description

A

PV array

B

String-Combiner Box

C

Inverter with integrated AC Disconnect and DC Switch

D

External transformer

E

Utility grid