SMA SC 500CP-US-10 600V User Manual
Page 91

SMA America, LLC
13 Parameters
Operating Manual
SCCP-US-BE-US_en-52
91
P-W
Limits active power in kW
The active power cannot
exceed Pmax.
0 kW to 1,000 kW
SC 500CP-US-10
550 kW
SC 500CP-US-10 600V
550 kW
SC 630CP-US-10
700 kW
SC 720CP-US-10
792 kW
SC 750CP-US-10
825 kW
SC 800CP-US-10
880 kW
SC 850CP-US-10
935 kW
SC 900CP-US-10
990 kW
P-WNom
Limits active power in %
0% to 100%
‒
100%
WCtlHzMod**
Frequency control
setpoint
Off
Deactivated
Off
CurveHys
Procedure with hysteresis
Curve
Procedure without
hysteresis
Start of frequency control
40 Hz to 70 Hz
‒
60.2 Hz
[50.2 Hz]
End of frequency control
40 Hz to 70 Hz
‒
60.05 Hz
[50.05 Hz]
P-HzStopMin**
Minimum frequency at
end point of frequency
control
40 Hz to 70 Hz
‒
60.05 Hz
[50.05 Hz]
P-WGra**
Gradient of power
reduction
1%/Hz to 100%/Hz
‒
40%/Hz
Qlimit*
Reactive power of device
0 kVAr to 332 kVAr
SC 500CP-US-10
332 kVAr
0 kVAr to 332 kVAr
SC 500CP-US-10 600V
332 kVAr
0 kVAr to 417 kVAr
SC 630CP-US-10
417 kVAr
0 kVAr to 477 kVAr
SC 720CP-US-10
477 kVAr
0 kVAr to 497 kVAr
SC 750CP-US-10
497 kVAr
0 kVAr to 530 kVAr
SC 800CP-US-10
530 kVAr
0 kVAr to 561 kVAr
SC 850CP-US-10
561 kVAr
0 kVAr to 594 kVAr
SC 900CP-US-10
594 kVAr
Name
Description
Value/range
Explanation
Default
value