SMA SC 500CP-US-10 600V User Manual
Page 97

SMA America, LLC
13 Parameters
Operating Manual
SCCP-US-BE-US_en-52
97
Voltage at point 2
80% to 120%
‒
100%
Time setting of the
characteristic curve point
1 s to 60 s
‒
10 s
Q-VArTmsVtg**
Delay of line voltage
1 s to 60 s
‒
10 s
Q-EnaTmsVtg**
Connection delay of line
voltage
Off
‒
Off
On
‒
WGra**
Active power change
gradient
0.17%/s to 100%/s
‒
100%/s
WGraEna**
Activation of the active
power change gradient
Off
Deactivated
Off
On
Activated
WGraRecon**
Active power change
gradient
0.17%/s to 100%/s
‒
100%/s
WGraReconEna** Activation of the
decoupling protection
ramp for reactivation
Off
Deactivated
Off
On
Activated
P-VtgGraNom
Active power gradient
with voltage-dependent
active power limitation
0.017%/s to
100.000 %/s
‒
0.166%/s
P-VtgEna
Activation of the
voltage-dependent active
power limitation
Off
Deactivated
Off
On
Activated
P-VtgNomP1
Voltage at point 1
100% to 120%
‒
110%
P-VtgNomP2
Voltage at point 2
90% to 120%
‒
100%
P-VtgAtMin
Minimum active power
with voltage-dependent
active power limitation
0% to 100%
‒
20%
PwrApLimitPrio***
Prioritization of active
power or reactive power
PrioPwtRt
Prioritization of reactive
power
PrioPwtRt
PrioPwtAt
Prioritization of active
power
SDLimComSrc***
Selection of the SDLimit
source
CAN
COM
UART
UART
Via SMA Net
P-WSubVal
Replacement value for
the active power
limitation outside of
normal feed-in operation
during communication
disturbance
0 kW to 1,000 kW
‒
990 kW
Name
Description
Value/range
Explanation
Default
value