13  Parameters

Operating Manual

SCCP-US-BE-US_en-52

97

Q-VolNomP2**

Voltage at point 2

80% to 120%

100%

Q-VArTmsSpnt**

Time setting of the

characteristic curve point

1 s to 60 s

10 s

Q-VArTmsVtg**

Delay of line voltage

1 s to 60 s

10 s

Q-EnaTmsVtg**

Connection delay of line

voltage

Off

Off

On

WGra**

Active power change

gradient

0.17%/s to 100%/s

100%/s

WGraEna**

Activation of the active

power change gradient

Off

Deactivated

Off

On

Activated

WGraRecon**

Active power change

gradient

0.17%/s to 100%/s

100%/s

WGraReconEna** Activation of the

decoupling protection

ramp for reactivation

Off

Deactivated

Off

On

Activated

P-VtgGraNom

Active power gradient

with voltage-dependent

active power limitation

0.017%/s to

100.000 %/s

0.166%/s

P-VtgEna

Activation of the

voltage-dependent active

power limitation

Off

Deactivated

Off

On

Activated

P-VtgNomP1

Voltage at point 1

100% to 120%

110%

P-VtgNomP2

Voltage at point 2

90% to 120%

100%

P-VtgAtMin

Minimum active power

with voltage-dependent

active power limitation

0% to 100%

20%

PwrApLimitPrio***

Prioritization of active

power or reactive power

PrioPwtRt

Prioritization of reactive

power

PrioPwtRt

PrioPwtAt

Prioritization of active

power

SDLimComSrc***

Selection of the SDLimit

source

CAN

COM

UART

UART

Via SMA Net

P-WSubVal

Replacement value for

the active power

limitation outside of

normal feed-in operation

during communication

disturbance

0 kW to 1,000 kW

990 kW

Name

Description

Value/range

Explanation

Default

value