11  Troubleshooting

Operating Manual

SCCP-US-BE-US_en-52

79

Behavior of the

inverter

Depends on the severity of the disturbance

Disturbance

level S1,

Disturbance

level S2

Warning (W)

The inverter has displayed a warning that does not influence the

behavior of the inverter.

Time

The inverter has detected an error and switches into the "Fault"

operating state.
In the process, the AC contactor and the DC switching device

open. The inverter does not feed into the grid for the defined

time.
The time specifies how long the error will be displayed on the

touch display and saved in the inverter as an error. If the time

has elapsed, the error is no longer shown on the touch display.

The inverter then checks whether the cause of the error has been

rectified.
If the cause of the error still exists after the time has expired or

the error has been acknowledged, the error is occurs again and

the inverter remains in the "Fault" operating state.

Acknowledge (A) The inverter switches to the "Fault" operating state and opens

the AC contactor and the DC switching device.

The inverter does not feed in until the error is acknowledged

manually.
When the error has been acknowledged, it is no longer shown

on the touch display. The inverter then checks whether the cause

of the error has been rectified.
If the error is no longer present, it is deleted from the memory.

If the cause of the error is still present after the error has been

acknowledged, the error occurs again.

Day change (D)

The inverter switches to the "Fault" operating state and opens

the AC contactor and the DC switching device.

The inverter does not feed into the grid.
The error message is automatically reset when the day changes.

If the error has been reset, it is no longer shown on the touch

display. The inverter then checks whether the cause of the error

has been rectified.
If the error is no longer present, it is deleted from the memory. If

the cause of the error is still present after the day has changed

or after the error has been acknowledged, the error occurs

again.

Plant-spec. (C)

The inverter switches to the "Fault" operating state and opens

the AC contactor and the DC switching device. The inverter

does not feed into the grid. How long the inverter remains in this

state depends on plant-specific influencing factors.
If the time has elapsed, the error is no longer shown on the touch

display. The inverter then checks whether the cause of the error

has been rectified. If the error is no longer present, it is deleted

from the memory.

Reset (R)

The control is restarted. The relays are checked and the control's

voltage supply is switched off. This process requires less than one

minute. While the control is powered up, the regular waiting times

of the inverter for grid monitoring are maintained.

Information

Level

Behavior

Explanation