11 Troubleshooting
Operating Manual
SCCP-US-BE-US_en-52
83
11.4.4 Error Number 60xx to 90xx ‒ Disturbance on the inverter
Error no.
Explanation
Behavior of the
inverter
Corrective measures
S 1
S 2
R
6002
Calibration data cannot be loaded.
‒
‒
‒
• Contact the SMA Service Line.
6113
Data block cannot be loaded from the
EEPROM or the channel list has changed
(e.g. after a firmware update)
‒
‒
‒
6115
Hardware limiting values on the
D/A converters cannot be set.
5 min
5 min
x
6116
Real-time clock is not initialized.
‒
‒
‒
6117
Device address not recognized.
5 min
5 min
x
6119
The data structure for the exchange
between the operation control unit and the
digital signal processor is invalid.
5 min
5 min
x
6120
Waiting for an answer from the OCU
30 s
‒
‒
6121
Waiting for an answer from the DSP
30 s
‒
‒
6122
Ten internal monitoring errors have
occurred in succession.
‒
5 min
‒
6128
General error
5 min
5 min
‒
6404
Overcurrent on the L1, L2 or L3 line
conductors.
30 s
5 min
x
6405
Overvoltage in the DC link.
30 s
5 min
x
6410
24 V voltage supply is invalid.
5 min
5 min
x
6417
15 V voltage supply is invalid.
5 min
5 min
x
• Contact the SMA Service Line.
6418
Overtemperature on the inverter bridge.
5 min 15 min
x
6422
The inverter bridge is in an undefined state. 30 s
5 min
x
6423
Overtemperature detected in the switch
cabinet.
5 min 30 min
x
6425
Synchronization error with the utility grid.
30 s
5 min
x
6427
Sensor error of the DC voltage
measurement.
30 s
C
x
6440
Hermetic protection of the transformer no
longer in place.
30 s
5 min
‒
• Check external transformer.
6441
Sensor error occurred during measurement
of the DC voltage.
30 s
30 s
‒
• Contact the SMA Service Line.
6443
An unspecified error has occurred in the
digital signal processor.
30 s
‒
‒
6447
Self-test in the inverter bridge failed.
A
A
‒