11 Troubleshooting
SMA America, LLC
84
SCCP-US-BE-US_en-52
Operating Manual
6448
Insulation monitoring delivers
non-permitted values.
W
W
‒
• Check insulation monitoring.
6451
Measured AC voltage from the
inverter is less than the voltage from the
utility grid
W
W
‒
6452
Measured AC voltage from the utility grid
is less than the voltage from the
inverter
W
W
‒
6453
AC voltage in the grid limits monitor is
mismatched
W
W
‒
6454
AC current is mismatched
W
W
‒
6455
AC voltage is mismatched
W
W
‒
6456
DC link precharging switch is faulty
W
W
‒
6457
Capacitor self-test has failed
A
A
‒
6461
The insulation monitoring device has not
adopted the threshold
15 mi
n
15 min
x
• Set the threshold in parameter
RisoCtlWarn.
6501
Internal temperature in the inverter is too
high.
30 s
1 min
‒
• Make sure that the fans are
working properly.
• Clean the fans.
• Clean dirty fan inlets and
ventilation plates.
6502
The temperature of the inverter bridge is
too high.
30 s
1 min
‒
6508
The outside temperature is too high.
30 s
1 min
‒
6605
Fast stop has tripped.
30 s
1 min
‒
• Contact the SMA Service Line.
7001
Cable break or short circuit at the
inverter temperature sensor.
‒
‒
‒
• Check the wiring of the
temperature sensor.
• Contact the SMA Service Line.
7002
Cable break or short circuit at the
inverter temperature sensor.
‒
‒
‒
7006
Cable break or short circuit at the
inverter temperature sensor.
‒
‒
‒
7501
Internal fan is faulty.
‒
‒
‒
• Make sure that the fans are
working properly.
• Clean the fans.
• Clean dirty fan inlets and
ventilation plates.
7502
Internal fan is faulty.
‒
‒
‒
7503
Stack fan is faulty.
‒
‒
‒
7507
Motor-protective circuit-breaker of the fan
has tripped.
‒
‒
‒
7601
Internal inverter error.
30 s
1 min
x
• Contact the SMA Service Line.
7602
An internal communication error has
occurred.
30 s
1 min
x
7605
An internal communication error has
occurred.
30 s
1 min
x
Error no.
Explanation
Behavior of the
inverter
Corrective measures
S 1
S 2
R