13  Parameters

Operating Manual

SCCP-US-BE-US_en-52

93

Q-VArMod**

Parameters for the

reactive power setpoint

procedure

Off

Sets reactive power to

0 kVAr and displacement

power factor cos φ to 1

Off

VArCtlCom

Specifies reactive power

via external control unit

PFCtlCom

Specifies the

displacement power

factor cos φ and the

excitation of the

displacement power

factor via an external

control unit

VArCnst

Specifies reactive power

in kVAr via the parameter

Q-VAr

VArCnstNom

Specifies reactive power

in % via the parameter

Q-VArNom

VArCnstNomAnIn

Specifies reactive power

at the analog input

QExlSpnt via the control

unit

PFCnst

Manually specifies the

displacement power

factor cos φ and the

excitation of the

displacement power

factor via the parameters

PF-PF and PF-PFExt

PFCnstAnIn

Specifies the

displacement power

factor cos ϕ at the analog

input QExlSpnt via the

control unit

PFCtlW

Specifies the

displacement power

factor cos φ depending

on the feed-in power

VArCtlVol

Specifies reactive power

depending on the line

voltage

VArCtlVolHystDb

Specifies reactive power

depending on the line

voltage (Q = f(V)

characteristic curve)

VArCtlVolHysDbA

(for Italy)

Name

Description

Value/range

Explanation

Default