SMA SC 500CP-US-10 600V User Manual
Page 93

SMA America, LLC
13 Parameters
Operating Manual
SCCP-US-BE-US_en-52
93
Parameters for the
reactive power setpoint
procedure
Off
Sets reactive power to
0 kVAr and displacement
power factor cos φ to 1
Off
VArCtlCom
Specifies reactive power
via external control unit
PFCtlCom
Specifies the
displacement power
factor cos φ and the
excitation of the
displacement power
factor via an external
control unit
VArCnst
Specifies reactive power
in kVAr via the parameter
Q-VAr
VArCnstNom
Specifies reactive power
in % via the parameter
Q-VArNom
VArCnstNomAnIn
Specifies reactive power
at the analog input
QExlSpnt via the control
unit
PFCnst
Manually specifies the
displacement power
factor cos φ and the
excitation of the
displacement power
factor via the parameters
PF-PF and PF-PFExt
PFCnstAnIn
Specifies the
displacement power
factor cos ϕ at the analog
input QExlSpnt via the
control unit
PFCtlW
Specifies the
displacement power
factor cos φ depending
on the feed-in power
VArCtlVol
Specifies reactive power
depending on the line
voltage
VArCtlVolHystDb
Specifies reactive power
depending on the line
voltage (Q = f(V)
characteristic curve)
VArCtlVolHysDbA
(for Italy)
Name
Description
Value/range
Explanation
Default
value