13 Parameters
SMA America, LLC
90
SCCP-US-BE-US_en-52
Operating Manual
13 Parameters
This section provides you with an overview of the parameters of all the components in the PV plant that you can display
and change via the user interface.
13.1 Sunny Central Inverter
13.1.1 Power Limitation
Name
Description
Value/range
Explanation
Default
value
Plimit*
Nominal device power
0 kVA to 550 kVA
SC 500CP-US-10
550 kVA
0 kVA to 550 kVA
SC 500CP-US-10 600V
550 kVA
0 kVA to 700 kVA
SC 630CP-US-10
700 kVA
0 kVA to 792 kVA
SC 720CP-US-10
792 kVA
0 kVA to 825 kVA
SC 750CP-US-10
825 kVA
0 kVA to 880 kVA
SC 800CP-US-10
880 kVA
0 kVA to 935 kVA
SC 850CP-US-10
935 kVA
0 kVA to 990 kVA
SC 900CP-US-10
990 kVA
Pmax**
Limitation of the nominal
power of the inverter
0 kW to 550 kW
SC 500CP-US-10
550 kW
0 kW to 550 kW
SC 500CP-US-10 600V
550 kW
0 kW to 700 kW
SC 630CP-US-10
700 kW
0 kW to 792 kW
SC 720CP-US-10
792 kW
0 kW to 825 kW
SC 750CP-US-10
825 kW
0 kW to 880 kW
SC 800CP-US-10
880 kW
0 kW to 935 kW
SC 850CP-US-10
935 kW
0 kW to 990 kW
SC 900CP-US-10
990 kW
P-WMod**
Specification of the
procedure for active
power limitation
Off
Limits active power to
Pmax
Off
WCtlCom
Limits active power via an
external control unit
WCnst
Limits active power in kW
via the P-W parameter
WCnstNom
Manually limits the active
power in % (P-W) via
communication devices,
such as the SC-COM
WCnstNomAnIn
Limits active power in % at
the analog input
WCnstNomDigIn
Limits active power at the
digital input
This procedure is not
supported.